9. Operator responsibility

You bought a high quality product with a long life 

time. To assure the function every technical equip-

ment needs to be serviced. 

Regular  back  washing  and  checks  oft  he  filter,  as 

well as leak tightness checks has to be done by the 

operater. According to DIN 1988-200 the filter has 

to be regularly visual inspected, not later than 2 

months. The filter has to be checked of leak tightness 

and contamination. The filterelement has to be peri-

odically, depending on operating conditions, but at 

least every 6 months changed.

Maintenance periods (change of parts): 

sealing every  

 

3 years

Manometer  

 

every 6 years

Pressure reducer element (11)  every 6 years 

According to DIN EN 806-5, maintenance must be

carried out by expert technical staffs who also re-

place the parts subject to wear and tear. We recom-

mend closing a maintenance contract. This is carried 

out by the installer or manufacturer.

Qualified staff:

 The product may only be installed, 

commissioned and serviced by skilled personnel. 

Only trained persons are allowed to operate and 

use it.

Trained person:

 Has received instruction and stu-

died the information in this document concerning 

the tasks entrusted to him/her, and the possible risks 

in the event of inappropriate behaviour.

Skilled personnel:

 Based on the professional training 

received, knowledge and experience, and know-

ledge of the relevant definitions, is qualified to install 

the product, to commission and to service it.

10. Technical data

Protector mini HWS C/R

Typ 

HWS C/R ½“

HWS C/R ¾“

HWS C/R 1“

HWS H/R ½“

Nominal connection width

DN 

15 

20

25

15

Flow rate** 

m

³

/h 

1,6

2,8

3,7

1,6

Output pressure after pressure 

reducing valve 

bar

2 – 6

Admission width

µm

100*

Nominal pressure (PN)

bar 

16

Operating pressure, min./max.

bar

1,5 during the flushing / 16

Water temperature, min./max.

°C 

5 / 30

5 / 70

Ambient temperature, min./max.

°C 

5 / 40

Connection thread A

G ½"

G ¾"

G 1"

G ½"

Connection thread B

 

G ¾"

G 1"

5

/

 

4

"

G ¾"

Total length C

mm 

80

90

100

80

Height D

mm

170

170

170

170

Total length E

mm

130

154

180

130

Height F

mm

262

330

330

262

Art.-Nr.

810548

810549

810550

810560

EAN-Code

9022000105487 9022000105494 9022000105500 9022000105609

*810599 HWS C/R ½"     

30 µm Filterelement,  

without screw connection  

(EAN 9022000105999)
**according to DIN EN 1567

Summary of Contents for Protector mini HWS C/R 1

Page 1: ...y work on the device you should read the fitting and operating instructions carefully and follow them While ourdata sheets and brochures should provide advice to the best of our knowledge the content...

Page 2: ...ht haben Thank you very much for the con fidence that you have shown in us by purchasing a BWT appliance Nous vous remercions de votre confiance pour l achat d un appareil BWT Vi ringraziamo per la fi...

Page 3: ...4 2 1 Filtration 4 2 2 Druckminderer 4 3 Funktion 4 3 1 Filtration 4 3 2 Druckminderer 4 4 Einbauvorbedingungen 4 5 Einbau 5 6 Inbetriebnahme 5 7 Bedienung 5 8 Gew hrleistung 5 9 Betreiberpflichten 6...

Page 4: ...kt Ein gleich m iger und nicht zu hoher Druck schont Armaturen und Ger te in der gesamten Hauswasserinstallation hilft bis zu 50 Wasser zu sparen und minimiert die Ger uschentwicklung Wir empfehlen de...

Page 5: ...f ver ndern Regelbereich 2 6 bar Drehen im Uhrzeigersinn h herer Hinterdruck Drehen gegen den Uhrzeigersinn geringerer Hinter druck Die Anzeige f r den Hinterdruckeinstellwert 8 ist ein Richtwert W hr...

Page 6: ...n zu erfolgen Qualifiziertes Personal Nur Fachpersonal darf das Produkt installieren in Betrieb nehmen und Instand halten Die Bedienung und der Gebrauch hat durch unterwiesene Personen zu erfolgen Unt...

Page 7: ...ltration 8 2 2 Pressure reducer 8 3 Function 8 3 1 Filtration 8 3 2 Pressure reducer 8 4 Installation conditions 8 5 Installation 9 6 Startup 9 7 Operation 9 8 Warranty 9 9 Operator responsibility 10...

Page 8: ...k pressure e g 3 bar A uniform not too high pressure preserves fittings and devices in the entire domestic water installation helps to save up to 50 of water and minimises noise evolution We recom men...

Page 9: ...ssure loosen the locking screw 6 and turn the rotary knob 7 The back pressure can be changed by turning the setting knob 7 control range 2 6 bar Clockwise rotation higher back pressure Anti clockwise...

Page 10: ...rained persons are allowed to operate and use it Trained person Has received instruction and stu died the information in this document concerning the tasks entrusted to him her and the possible risks...

Page 11: ...2 R ducteur de pression 12 3 Fonctionnement 12 3 1 Filtration 12 3 2 R ducteur de pression 12 4 Conditions de montage 12 5 Installation 13 6 Mise en service 13 7 Utilisation 13 8 Garantie 13 9 Obliga...

Page 12: ...mple une pression de 3 bar apr s d tente Une pression constante et mod r e prot ge la robinetterie et les appareils raccord s au r seau d eau Nous recommandons l installation d un r ducteur de pressio...

Page 13: ...t tre plusieurs fois bri ve ment ouvert puis ferm Pendant la prise d eau la pression aval baisse temporairement 7 Utilisation V rifier et rincer le filtre r guli rement tous les deux mois cf DIN 1988...

Page 14: ...ruite oralement et par le biais des pr sentes instructions des t ches qui lui reviennent et des ventuels risques susceptib les de survenir en cas de comportement inad quat Personnel technique Celui ci...

Page 15: ...16 2 2 Riduttore di pressione 16 3 Funzionamento 16 3 1 Filtrazione 16 3 2 Riduttore di pressione 16 4 Premesse all installazione 16 5 Installazione 17 6 Messa in funzione 17 7 Utilizzo 17 8 Garanzia...

Page 16: ...antenere la pressione in uscita entro i valori impostati ad es 3 bar Una pressione costante e non eccessiva garantis ce l efficienza della rubinetteria e delle apparecchia ture di tutto l impianto idr...

Page 17: ...opola campo di regolazione 2 6 bar Rotazione in senso orario aumento della pressione in uscita Rotazione in senso antiorario diminuzione della pressione in uscita Durante la regolazione si consiglia d...

Page 18: ...uso devono essere affidati a persone con appropriata for mazione Persona con appropriata formazione ha ricevuto un apposito insegnamento e una formazione effettuata in base alle informazioni contenute...

Page 19: ...20 2 1 Sz r s 20 2 2 Nyom scs kkent 20 3 M k d s 20 3 1 Sz r s 20 3 2 Nyom scs kkent 20 4 A be p t s el felt telei 20 5 Be p t s 21 6 zembe helyez s 21 7 Kezel s 21 8 J t ll s 21 9 Az zemeltet k tele...

Page 20: ...gadozik Az egyenletes s nem t l nagy nyom s k m li a szerelv nyeket s k sz l keket az eg sz h zi v zrendszerben ak r 50 vizet seg t megtakar tani s minim lisra cs kkenti a keletkez zajt 4 bar el nyom...

Page 21: ...lyoz si tartom ny 2 6 bar Az ramutat j r si ir ny ba forgatva nagyobb ellennyom s Az ramutat j r si ir ny val szembe forgatva kisebb ellennyom s Az ellennyom sra megadott be ll t si rt k 8 ir ny rt k...

Page 22: ...haszn lj k Szakk pzett szem lyzet A term ket csak szaksze m lyzetnek szabad felszerelnie zembe helyeznie s karbantartania A term ket betan tott szem lyek kezelj k s haszn lj k Betan tott szem ly okta...

Page 23: ...4 2 1 Filtrace 24 2 2 Reduk n ventil 24 3 Funkce 24 3 1 Filtrace 24 3 2 Reduk n ventil 24 4 P edb n podm nky pro mont 24 5 Mont 25 6 Uveden do provozu 25 7 Obsluha 25 8 Z ruka 25 9 Povinnosti provozov...

Page 24: ...st Doporu ujeme mont reduk n ho ventilu od vstupn ho tlaku 4 bary 3 Funkce 3 1 Filtrace Surov voda proud p es vstup do filtru a tam zven dovnit filtra n vlo kou k v stupu ist vody P itom jsou ciz stic...

Page 25: ...olikr t kr tce otev en a zase zav en P i odb ru vody p echodn klesne v stupn tlak V stupn tlak nesm in v ce ne 80 otev rac ho tlaku bezpe nostn ho ventilu tepl vody DIN 1988 200 7 Obsluha Filtr v prav...

Page 26: ...u en osoby Pou en osoba Osoba byla v r mci kolen a informac z tohoto n vodu zpravena o j p id len ch loh ch a mo n ch nebezpe ch p i nespr vn m chov n Odborn person l Je schopn na z klad sv ho odborn...

Page 27: ...ltracja 28 2 2 Reduktor ci nienia 28 3 Spos b dzia ania 28 3 1 Filtracja 28 3 2 Reduktor ci nienia 28 4 Wst pne warunki monta u 28 5 Monta 29 6 Uruchomienie 29 7 Eksploatacja 29 8 Gwarancja 29 9 Obowi...

Page 28: ...i urz dzenia w ca ej domowej instalacji wodnej pomaga zaos zcz dzi do 50 wody i minimalizuje powstawanie szum w Monta reduktora zalecamy przy ci nieniu wlotowym wynosz cym minimum 4 bary 3 Spos b dzia...

Page 29: ...a wy sze ci nienie wyj ciowe Obracanie przeciwnie do ruchu wskaz wek zegara ni sze ci nienie wyj ciowe Wskazanie warto ci nastawczej ci nienia wyj ciowego 8 jest warto ci wyj ciow Podczas regulacji na...

Page 30: ...ywalnych musi by przeprowadzana przez wyspecjalizowany per sonel instalator lub autoryzowany serwis Zalecane jest zawarcie umowy serwisowej z instalatorem lub z autoryzo wanym serwisem Obs uga i eksp...

Page 31: ...31 RU 1 32 2 32 2 1 32 2 2 32 3 32 3 1 32 3 2 32 4 32 5 33 6 33 7 33 8 34 9 34 10 35...

Page 32: ...Protector mini HWS C R 1 p 2 810599 3 810560 4 5 6 7 8 9 10 11 12 1 4 2 2 1 Protector mini HWS 2 2 16 3 50 3 3 1 30 100 1 6 3 2 7 8 4 AVB Wasser V 12 2 6 7 8 9 10 11 3 2 5 1 H R C R 072843 4 Art Nr 33...

Page 33: ...33 RU 5 10 DIN EN 1988 200 20 6 8 10 4 6 7 7 2 6 80 DIN 1988 200 7 1 2 DIN 1988 200 DIN 1988 200 21 H R 20 mm...

Page 34: ...34 RU 8 9 DIN 1988 200 2 1 6 1 3 DIN EN 806 5...

Page 35: ...0 PN 16 min max 1 5 w hrend der Sp lung 16 min max C 5 30 5 70 min max C 5 40 A G G G 1 G B G G 1 G 5 4 G C 80 90 100 80 D 170 170 170 170 E 130 154 180 130 F 262 330 330 262 810548 810549 810550 8105...

Page 36: ...01 304 Warszawa Phone 48 22 53357 00 Fax 48 22 53357 19 E Mail bwt bwt pl BWT France SAS 103 rue Charles Michels F 93206 Saint Denis Cedex Phone 33 1 49 2245 00 Fax 33 1 49 2245 45 E Mail bwt bwt fr...

Reviews: