background image

Vacuum pump

INSTALLER

Humid air left inside the refrigerant circuit can cause com-
pressor malfunction. After having connected the indoor 
and outdoor units, bleed the air and humidity from the 
refrigerant circuit using a vacuum pump.

(1) Unscrew and remove the caps from the 2-way and 3-

way valves.

(2) Unscrew and remove the cap from the service valve.
(3) Connect the vacuum pump hose to the service valve. 
(4) Operate the vacuum pump for 10-15 minutes until an 

absolute vacuum of 10 mm Hg has been reached.

(5) With the vacuum pump still in operation, close the 

low-pressure knob on the vacuum pump coupling. Stop 
the vacuum pump.

(6) Open the 2-way valve by 1/4 turn and then close it 

after 10 seconds. Check all 

the joints for leaks using 

liquid soap or an electronic leak device.

(7) Turn the body of the 2-way and 3-way valves. Discon-

nect the vacuum pump hose.

(8) Replace and tighten all the caps on the valves.

BLEEDING

INSTALLER

INDOOR

UNIT

Vacuum pump

 

Vacuum pump

Connect to the

indoor unit

Location

Twisting moment (N.m)

35-40

60-65

45-50

70-75

ĭ

2

ĭ

9

Diameter (mm)

ĭ

.52

ĭ

6

15-20

ĭ

(9) If the specification of outdoor unit gas valve is 3/8

     but curstomer needs to install 1/2

indoor unit so that 

     it is need to use a “pipe joint subassembly” (Code 06643008) 
     to make a conversion joint with outdoor unit gas valve and 
     connection pipe, as show in following.

conversion joint

Refrigerant fluid direction of flow

3-way valve

2-way valve

Ser vice 
inlet

(2) Turn
(8) Secure

(7) Turn to open fully

(2) Turn

(8) Secure

Valve cap

(6) Open by 1/4 turn

(7) Turn to open fully

(2) Turn

(8) Secure

Valve cap

Drain-water hole

Bottom frame

Drain plug

Hose (available commercially,
inner dia. 16mm)

Drain connecter

Use bolts to secure the unit to a flat, solid floor.
When mounting the unit on a wall or the roof, make
sure the support is firmly secured so that it cannot
move in the event of intense vibrations or a strong
wind.

Do not install the outdoor unit in pits or air vents
Installing the pipes

Install the drain fitting and the drain hose(for
model with heat pump only)

Condensation is produced and flows from the outdoor unit 

when the appliance is operating in the heating mode. In order
not to disturb neighbours and to respect the environment,
install a drain fitting and a drain hose to channel the conden-
sate water. Install the drain fitting and rubber washer on the 
outdoor unit chassis and connect a drain hose to it as shown 
in the figure.

Use suitable connecting pipes and equipment for the 
refrigerant R410A.

Wrap all the  refrigerant pipes and joints.

Tighten the connections using two wrenches working 

in opposite directions.

Caution: Installation Must be Performed in Accordance

with the NEC/CEC by Authorized Personnel Only

Models(m)

18K

24/30K

Max. connection pipe length

20

70

Max. connection pipe length(Simple
one indoor unit)

10

20

The refrigerant pipes must not exceed the maximum 

heights 5m(18K) or 

10m(24K&30K).

INSTALLING THE OUTDOOR UNIT

7

Summary of Contents for BESM-24AO23

Page 1: ...sing BuƩerfly Energy Systems please review installaƟon guide before installaƟon and retain for future reference BuƩerfly Energy Systems Air Intelligence Series InstallaƟon Guide For Outdoor MulƟ Head Systems BESM 24AO23 ...

Page 2: ......

Page 3: ...pliance may be changed without notice CONFORMITY AND RANGE GENERAL INFORMATION GENERA L INFORMATION Please read this owner s manual carefully before operating the unit and keep it carefully for consultation Product diagrams in this manual may appear different from your actual model The air conditioner you have purchased conforms with the following American Directives UL1995 Only use the air condit...

Page 4: ... enter any ventilation or exhaust opening This many cause injury electrical shock fire or damage to the appliance 6 To prevent a possible fire do not block air intakes or exhaust in any manner 7 Do not stand or rest any object on top of the appliance 8 Do not operate if there is any damage to the appliance 9 The installation repairs and modifications to the appliance are only to be performed by a ...

Page 5: ...t happen Wetting of air conditioner may cause the risk of electric shock Make sure not to wash your air conditioner in any case Volatile liquids such as thinner or gasoline will cause damage to the appearance of air conditioner Only use soft dry cloth moist cloth clean the air conditioner cabinet Collection of such waste separately for special treatment is necessary or its service agent or a simil...

Page 6: ...ING TEMPERATURE RANGE GENERAL INFORMATION 4 TECHNICAL DATA GENERA L INFORMATION P L A B H Minimum power cable section 40 4 0 g mm mm mm mm mm L P H A B Fuse or air switch 2200 890 362 700 560 368 MODE BESM 24AO23 208 230V 1 60Hz mm2 Refrigerant gas R410A Electrical data Electricity supply Size and clearance c ...

Page 7: ...onding to each other respective The appliance shall be installed in accordance with national wiring regulations Do not install the outdoor unit where it is exposed to the sunlight Note the above figures are only intended to be a simple e h t o t d n o p s e r r o c t o n y a m d n a e c n a i l p p a e h t f o m a r g a i d appearance of the units that have been purchased To the power supply To un...

Page 8: ...ackaging check that the contents are intact and complete The outdoor unit must always be kept upright Handling must be done by suitably equipped qualified technical personnel using equipment that is for suitable the weight of the appliance 6 ...

Page 9: ...Refrigerant fluid direction of flow 3 way valve 2 way valve Service inlet 2 Turn 8 Secure 7 Turn to open fully 2 Turn 8 Secure Valve cap 6 Open by 1 4 turn 7 Turn to open fully 2 Turn 8 Secure Valve cap Drain water hole Bottom frame Drain plug Hose available commercially inner dia 16mm Drain connecter Use bolts to secure the unit to a flat solid floor When mounting the unit on a wall or the roof m...

Page 10: ... wall 200cm Air outlet side or above 30cm Space to the cover or above or more Space to the cover 50cm INSTALLER Use suitable instruments for the refrigerant R410A Do not use any other refrigerant than R410A Do not use mineral oils to clean the unit Contact service center before installation to avoid the malfunction due to unprofessional installation When picking up and moving the units you must be...

Page 11: ...ecified on the nameplate The unit may bread down or the components may be burned out Are the lines and pipelines correctly installed The unit may bread down or the components may be burned out Has the unit been safely grounded Risk of electrical leakage Are the models of lines in conformity with requirements The unit may bread down or the components may be burned out Are there any obstacles near t...

Page 12: ...66129915030 ...

Reviews: