6 | Commissioning
20 / 32
0870168572_MV0310B_-0001_IM_en_MD
6.1.4.1 Parameter settings for exact pressure control
PID Control Settings
P3.13.1.1 PID Gain
If the value of the parameter is set to 100% a change of 10% in the error value causes
the controller output to change by 10%.
Preset value: 400%
P3.13.1.2 PID Integration Time
If this parameter is set to 1.00 second a change of 10% in the error value causes the
controller output to change by 10%/s.
Preset value: 0,5 s.
Nominal Values
P3.13.2.1 Keypad SP 1
Setting the nominal value in mbar.
Preset value: 400 mbar
Sleep Settings
Sleep will put the machine to sleep-mode when the pressure level is steady.
P3.13.5.1 SP 1 Sleep Frequency
This function will put the drive into sleep mode if the set point is reached and the out-
put frequency stays below the sleep limit for a longer time than set in the sleep delay
Preset value: 20,2 Hz
• do not set the value below 20,2 Hz, otherwise sleep-mode will be disabled.
P3.13.5.2 SP 1 Sleep Time Delay
Time of working at minimum frequency, before entering sleep-mode condition.
Preset value: 5s
P3.13.5.3 SP 1 Sleep Wake-Up Limit
Defines the PID feedback error limit for the wake-up function. The drive exits from
sleep-mode if the Error exceeds this value.
Preset value: 10,0 mbar