8. FILLING THE HEATING INSTALLATION
Table 6
Problem
Prevention
Possible installation damage due
to strains in the material caused
by temperature differences
Fill the heating installation only in cold conditions
(inlet temperature must not exceed 40 °C).
Danger of installation damage
due to accumulation of deposits
Condensate formation and tar
deposits may shorten boiler’s
operational life.
- Do not operate the heating boiler for a long period
of time in partial load mode
- The temperature at the boiler inlet must not be
less than 65°C, boiler water temperature must be
between 80 °C and 85 °C.
- Use the boiler for a short period to heat warm
water in the summer.
9. BOILER OPERATION
9.1. Loading and ignition the boiler
When ignition the boiler for the first time,
a condensate is formed which is later
drained (this is not a fault in the boiler).
Fuel is loaded in the combustion chamber
and it is recommended to load logs of
length equal to the combustion chamber
length and stack them tight inside with
least possible air gaps. The chamber door
as well as all inspection openings must be
closed and sealed. Open the thermostatic
draft regulator and chimney flap to ignite
the boiler. When boiler temperature reach
85°С, adjust intake air by the chimney
flap and boiler air-intake door flap. The
position of boiler air-intake door flap
adjust by thermostatic draft regulator.
When burning wood with moisture
content more than 20%, results in:
- significantly increases fuel consumption;
- not reach the desired power;
- lifetime of the boiler and chimney fall.
Do not open the flue damper
during boiler operation!
Maintain
operating
temperature between 80° C
and 90° C.
9.2. Adjust the boiler combustion by
thermostatic draft regulator
Adjusting.
Heat the boiler up to 80°С.
Control valve is placed in a position to
meet the temperature reading on the
thermometer. Red numbers and red
indicator point are valid for vertical
mounting.
Thermostatic regulator test.
Through the
control valve set temperature reading of
thermometer in the boiler. The flap must
be close whet the temperature reach
95°С.