INSTRUCTIONS FOR THERMOWELD GROUNDING CONNECTIONS TYPE CR-28, CR-33, CR-37 & CR-39 MOLDS

1.  SEE REVERSE SIDE FOR PREPARATION OF CABLE AND COPPER TUBE  

  OR PIPE.

2.  INSERT GRAPHITE TUBE INTO PIPE UNDER AREA TO BE WELDED AND   

  WEDGE INTO PLACE FOR A TIGHT FIT (SEE FIGURE 1).

3.  POSITION CABLE AND MOLD ON PIPE ABOVE THE GRAPHITE PLUG.     

  ON CR-28 MOLDS, MAKE SURE END OF CABLE IS IN THE CENTER OF    

  THE TAP HOLE AND FOR CR-37, BUTT END OF CABLE AGAINST PIPE.  FOR  

  CABLES THAT REST ON THE SURFACE OF THE PIPE, PACK CABLE OPENING  

  WITH PACKING MATERIAL TO PREVENT LEAKAGE OF MOLTEN METAL

4.  FOLLOW WELDING PROCEDURES ON THE BACK OF THIS SHEET. 

     (

NOTE:

 HANDLE CLAMPS MAY BE PLACED ON EITHER THE CABLE SIDE  

  OR THE OPPOSITE SIDE, WHICHEVER IS REQUIRED ON CR-28 TYPE MOLDS.)

FOR CABLE SIZE 1/0 & LARGER

CABLE IS OFF SURFACE

FOR CABLE SIZE #1 & SMALLER

CABLE IS ON SURFACE