Burn Tech GBVS 39/44/49 Instructions Manual Download Page 18

16

Venting Installation

A “B-type” venting system must be connected to the appliance 

for venting to outside of building. The following section is 

provided as a guide to a standard B-type vent installation.

 

Standing  codes  requirements  concerning  B-type  vent 

installations may vary within your state, province or local codes 

jurisdiction. Therefore, it is recommended that you check with 

your local building codes for specific requirements or in absence 

of local codes, follow Section 7.0 of the current National Fuel 

Gas Code ANSI Z223.1/NFPA 54 for Category I systems using 

double wall B-1 vent pipe.

 

This  gas  appliance  must  be  vented  to  the  outdoors  only 

and may not be terminated into an attic space or into a chimney 

flue servicing a solid fuel burning appliance.

 

This  appliance  may  be  vented  through  a  manufactured 

chimney system or a masonry chimney using a B-vent adapter 

or  a  chimney  liner  system  if  the  system  is  listed,  inspected 

and approved by local codes and/or building authorities. The 

examples shown in Fig. 2 are typical of most B-vent installations 

and codes practices.

Example 1:

 Shows the minimum allowable system height and 

lateral offset for an inclination of 60° or greater. 

 

Code specifies that offsets of 60° or greater are considered 

horizontal and must follow the 75% rule for lateral to total vertical 

system height.

 

Codes also allows only one offset in the total system when 

at 60° or greater.

 

The  total  vertical  height  in  this  example  represents  the 

minimum height of 8 ft. and therefore the allowable lateral is 6 

ft. when the 75% rule applies.

 

If the lateral length must exceed 75% then the system must 

be sized in accordance with the Category I venting tables.

Example 2:

 Shows a multiple offset each at a 45° inclination.

 

Multiple offsets are permitted if they do not exceed a 45° 

inclination. The total lengths of the two offsets are not required 

to meet the 75% allowable rule.

Figure 2

Example  3:

  Shows  a  single  offset  at  45°  of  inclination  and 

therefore the lateral length at 10 ft. of offset does not have to 

meet the 75% rule.

 

In each case the offsets must be supported and firestops 

must be positioned wherever the vent must pass through a sub-

floor, ceiling joist or an attic overhang.

 

The  vent  pipe  must  terminate  vertically  into  a  listed  type 

vent cap and extend a sufficient height through an approved 

roof flashing, roof jack or a roof thimble. At all points the listed 

clearances must be maintained.

 

Vent  terminations  must  be  located  in  accordance  with 

height and proximity rules of NFPA No. 54. 

 

These  rules  apply  to  vents  at  12”  diameter  or  less  and 

require a minimum height in accordance with the roof pitch and 

a minimum of 8 ft. distance from a vertical wall or obstruction 

(see Fig. 3).

 

If  venting  horizontally  through  a  side  wall  becomes 

necessary, a listed thimble approved for use with B-type vent 

must  be  used.  Check  with  your  local  codes  before  venting 

through a side wall.

 

Some  codes  areas  allow  the  use  of  existing  B-type  vent 

systems if the system is at or above the recommended diameter 

of the flue.

 

The  flue  connection  must  be  made  using  listed  B-type 

connectors and the existing system must be code inspected for 

damage and proper installation.

 

It  is  not  recommended  that  this  appliance  be  common 

vented  with  an  existing  gas  burning  appliance.  However,  if  it 

becomes necessary to common vent this appliance, the venting 

system must be sized and configured in accordance with the 

common  venting  guides  Appendix  G  of  the  current  National 

Fuel Gas Code NFPA No. 54/ANSI Z223.1.

Note:

  Before  connecting  this  appliance  to  an  existing  vent  

system or  a  common  venting  system, consult  with  your  local 

architect, planner, or building official.

Summary of Contents for GBVS 39/44/49

Page 1: ...0 standard Solid fuels shall not be burned in this fireplace This appliance must be vented vertically through the roof This appliance is not for installation in manufactured or mobile homes The instal...

Page 2: ...THIS PAGE INTENTIONALLY LEFT BLANK...

Page 3: ...YPE DO NOT REMOVE THIS LABEL See Burntech Installation Operating Instructions for this model Contact local building officials about restrictions and installation specifications in your area THIS FIREP...

Page 4: ...ponents Warning Failure to position the parts in accordance with these diagrams or failure to use only parts specifically approved with this appliance may result in property damage or personal injury...

Page 5: ...DESCRIPTION QTY 1 TFS39 1 TFS44 1 TFS49 1 HEARTH Left or Right 2 2 TFS39 2 TFS44 2 TFS49 2 REAR WALL 3 3 TFS39 3 TFS44 3 TFS49 3 SIDE WALL 7 3A TFS39 3A TFS44 3A TFS49 3A SIDE WALL with 4 opening for...

Page 6: ...ent parts and accessories as listed in these parts lists Before beginning installation be sure the burner system is complete by comparing its contents with this Parts List Parts may differ depending u...

Page 7: ...illustrations in this manual are for general reference only Do not scale drawings Actual design elements will vary from case to case Pay attention to specified minimum clearances to combustibles WARNI...

Page 8: ...accessories Use of other controls parts and accessories which are not designed for use with Burntech gas fireplaces is prohibited and will void all warranties certifications listings and building code...

Page 9: ...t reading these procedures will save you time and at the most it will prevent any malfunction that could result in property damage or serious injury Do not start the installation until you have checke...

Page 10: ...he addition of floor joists to align with the anchor brackets allows the brackets to be directly connected to the floor joists Note that additional floor joists may be required to support the weight o...

Page 11: ...at time of installation and used under dry conditions the deflection resulting from L 0 5D is permitted to be substituted for the deflection resulting from L D Note that Burntech cannot accept respons...

Page 12: ...washers GBVS 44 49 Eight 8 pieces 3 8 rebar x 36 long included with unit Eight 8 ea All thread x 12 long with nuts and washers ALL UNITS Three 3 90 lb bags of ready mix concrete with 1 4 or smaller ag...

Page 13: ...latness level if necessary Figure 13 1 2 away from edges 1 2 mortar bead typical Hearth section shown prepared for Right Side position Apply mortar bead to all mating surfaces Apply mortar to the rema...

Page 14: ...veled face lines up with the inward angles of the lintel sides Resulting top surfaces should be level Figure 20 Lower Dome Sides Rating Plate faces inside Verify that the smoke dome side front and rea...

Page 15: ...5 Fireplace Finishes Combustible Trim Clearances Mantel and Mantel Shelf Clearances As with any radiant heat fireplaces all Burntech Fireplaces must comply with building code safety clearances per uni...

Page 16: ...in an accident or malfunction If instructions are not followed the warranty on the product will become null and void 3 1 2 3 4 5 Note that the most important aspect of the installation is the maintena...

Page 17: ...1 One elbow begins the installation procedure and the second elbow is used to finish off each section In all likelihood a 30 degreeoffsetelbowwillprobablybethefirsthardwareusedoff the top of the ancho...

Page 18: ...lination Multiple offsets are permitted if they do not exceed a 45 inclination The total lengths of the two offsets are not required to meet the 75 allowable rule Figure 2 Example 3 Shows a single off...

Page 19: ...re scheduled to install the round top termination unit or any of the flashings or flues that will be exposed to outside weather conditions Venting terminals shall not be recessed into walls or siding...

Page 20: ...ch sensor pointed toward the room out of the fireplace Use six 6 drywalls screws to fasten it in place on the front most part of the firebox ceiling as shown through the six 6 pre drilled holes Attach...

Page 21: ...SOAPY WATER SOLUTION IF A LEAK IS DETECTED TIGHTEN CONNECTIONS AND TEST AGAIN NEVER USE AN OPEN FLAME TO CHECK FOR GAS LEAKS Insert a one way screw into the hole in the front of each bracket and tight...

Page 22: ...d the heat chambers facing the back of the fireplace Figure 35 Place the front log on the grate in front of the top burner pipe with the flat down and the heat chambers toward the burner pipe and the...

Page 23: ...the four 4 screws above and below the control panel face then pull the control panel out far enough to expose the test ports on the valve Figure 41 Unscrew the port marked IN part way and test CAUTION...

Page 24: ...ts a Check with a millivolt meter Should be 250 millivolts or more b Pilot flame making a blowing sound b Pilot needs adjusting see Checking and Adjusting the Pilot on page 22 c Generator wire leads a...

Page 25: ...ncrete slab The concrete strength and durability shall comply with Sections 1903 1904 and 1905 of the International Building Code IBC TABLE R402 2 MINIMUM SPECIFIED COMPRESSIVE STRENGTH OF CONCRETE MI...

Page 26: ...ly b Lines defining areas are approximate only Local conditions may be more or less severe than indicated by region classification A severe classification is where weather conditions result in signifi...

Page 27: ...ded at Burntech Fireplace Solutions s option Nothing in this warranty makes Burntech Fireplace Solutions or any affiliate thereof liable in any respect for any injury or damage to the building or stru...

Reviews: