Locate thermostat bulb in a cool place away from the appliance and preferably
outside of any inglenooks, to ensure it is sensing room air temperature.
•
Run appliance for 15 minutes, ensuring burner flames settle evenly.
•
A combustion analysis check should then be carried out. Using an analyser to
BS7927, first zero the equipment and sample the entire width of the combustion
product outlet.
Ratio of CO/CO2 should be less than 0.002 within 30 minutes.
(20ppm CO per 1% CO2) A reading of CO in the room centre should give a rise of
less than 9ppm
over ambient, peak reading. The catalyst is unlikely to need
replacement during the life of the appliance but if the combustion is suspect,
disconnect the appliance and contact the manufacturer. See the additional
information on testing.
11.
PARTS LIST
Part
Part No
Front Ceramic Coal
COA4241F
Rear Ceramic Coal
COA4241B
Oxypilot NG
Check if SIT or Seagas
Oxypilot LPG
Check if SIT or Seagas
Glass
GLA4140
Grill
GRI4240
90mm Freestanding Spacer
SPACERKIT
Remote Valve (Mertik)
VAL1921
Remote Handset & Receiver
VAL1924
Trim Backer
TRI4140
60mm INFILL SPACER
INF0140
Pebble Set
PEB4237F&B
USE ONLY GENUINE REPLACEMENT PARTS.
Parts ordered from our factory will normally take 5 – 7 working days to be delivered.
An ‘Express service’ is available upon request.
Due to our policy of continual improvement and development the exact accuracy of
descriptions and illustrations cannot be guaranteed.
Burley Appliances are the only company to bench run and thoroughly test every single Flueless
gas fire it produces. Burley is in the unique position of knowing that every appliance leaves the
factory in perfect working order.