9
ATTENTION
Pumps that do not stand steady or stable on
their own, should be mounted on a rigid
and stable base.
ATTENTION
Place the pump there where there is the
lowest risk for noise nuisance.
1. Place and install the pump on a level, stable surface in
a dry and frost-proof room.
2. Make sure that suf
fi
cient air can reach the cooling fan
of the motor. For this purpose the free space above the
cooling fan should be at least ¼ of the diameter of the
fan cover air intake.
3. Install the pump with counter
fl
anges. Pumps with non-
standardised connections; counter
fl
anges are delivered
separately.
4. Install a valve on the supply and on the delivery
connection of the pump.
5. If there is a chance that when the pump is standing still
the medium can
fl
ow back, it is advised to install a non-
return
valve.
6. Make sure that the inlet of the pump is never clogged.
F-1.1) Indicators:
The arrow (A) on the pump foot indicates the
fl
ow direction
of the liquid. The arrow (B) on the top bracket indicates the
rotating direction of the motor.
F-1.2) Install bypass:
Install a bypass if the pump operates against a closed
valve. The required capacity of the bypass is at least
10% of the optimum volume
fl
ow. At high operating
temperatures a higher volume
fl
ow is required. Refer to the
table “Minimum volume
fl
ows” in the paragraph “Working
range”
F-2) Mounting a motor on the pump:
ATTENTION
It is to be advised to use a special designed
BP Pumps motor. Before installing an other
brand/standard IEC-norm motor, BP Pumps
has to be consulted to judge the applicability.
The motor has to conform to the following conditions:
• Increased power output (to limit the standard installed
motor
power)
• Reinforced bearing at driven end (to withstand the axial
force)
• Fixed bearing at driven end (to minimize the axial play)
• Smooth shaft, no key lock (to improve the coupling grip
and to improve the motor balance)
The advised bearings per motor type are:
(HP)
Axial Bearing
(HP)
Co-axial Bearing
0.50
6203-2RS
7.50
6308-2Z-C3
0.75
6203-2RS
10.00
6308-2Z-C3
1.00
6204-2RS
15.00
7309-BEP
1.50
6204-2RS
20.00
7309-BEP
2.00
6305-2Z-C3
25.00
7309-BEP
3.00
6305-2Z-C3
30.00
7311-BEP
5.00
6306-2Z-C3
40.00
7312-BEP
50.00
7312-BEP
Summary of Contents for BPLHS Series
Page 22: ...22 Selection O ring and shroud BPV S F V 10 18 Selection O ring and shroud BPV S 2 4...
Page 32: ...32 SECTION S Sectional Drawings S 1 Sectional drawing BPV S C F 2 4 10 18...
Page 33: ...33 S 2 Sectional drawing BPV S C F 32 10 32 20...
Page 35: ...35 S 4 Sectional drawing BPV S C F 45 10...
Page 36: ...36 S 5 Sectional drawing BPV S C F 45 20 45 30 45 40 45 50 45 60 with cartridge seal...
Page 37: ...37 S 6 Sectional drawing BPV S C F 65...
Page 38: ...38 S 7 Sectional drawing BPV S C F 85...
Page 39: ...39 S 8 Sectional drawing BPVLHS 6...
Page 40: ...40 SECTION T Exploded Views T 1 Exploded View BPV S 2 4 10 18...
Page 41: ...41 T 3 Exploded View BPV S F 32 45...
Page 42: ...42 T 4 Exploded View BPV S F 32 45 with cartridge seal...
Page 43: ...43 T 5 Exploded View BPV S F 65...
Page 44: ...44 T 7 Exploded View BPLHS 6...
Page 54: ...Notes...