7.3.3
Wiring the 12...36 V DC electrical supply for a
8619 multiCELL
→
Use a filtered and regulated 12...36 V DC electrical power supply.
→
Wire the 12...36 V DC power supply on the main board "M0" of a 8619 multiCELL.
→
Connect the functional earth of the installation to the earth screw of the device (see section 5, Fig. 1) using a
lug with an eyelet, suitable for the M4 earth screw and earth conductor. Tighten to the torque of 1 N·m ±20%
(0,74 lbf·ft ±20%).
→
Connect the shielding on each wire to an "FE" (functional earth) terminal to guarantee the equipotentiality of
the installation.
12-36 VDC
+
-
V+
SUPPLY PWR OUT DI1
FE
DI2
DO2
DO1
AO1 AO2 FE
FE
V-
FE
+
-
FE
D+
D-
D+
D-
FE
I+
I-
I+
I-
FE
T+
T-
T+
T-
FE
Electrical power supply
Removable screw terminals, 21-positions, black
Fig. 13 : Wiring the 12...36 V DC electrical supply for a 8619 multiCELL
7.3.4
Wiring the 12...36 V DC electrical supply for a
8619 multiCELL WM DC
→
Use a filtered and regulated 12...36 V DC electrical power supply.
→
Use the rightmost cable gland for the electrical power supply cable.
→
Wire the 12...36 V DC power supply for a 8619 multiCELL WM on a terminal block marked 12...36 V DC.
→
Connect the functional earth of the installation to the earth screw of the device (see section 5, Fig. 2) using a
lug with an eyelet, suitable for the M4 earth screw and earth conductor. Tighten with a torque of 1 N·m ± 20%
(0,74 lbf·ft ±20%).
→
Connect the shielding on each wire to an "FE" (functional earth) terminal to guarantee the equipotentiality of
the installation.
48
Installationandwiring
Type 8619
English
Summary of Contents for 8619 multiCELL WM AC
Page 6: ...6 English ...
Page 12: ...12 Type 8619 English ...
Page 24: ...24 Type 8619 English ...
Page 40: ...40 Type 8619 English ...
Page 70: ...70 Installation and wiring Type 8619 English ...
Page 180: ...180 Type 8619 English ...
Page 192: ...192 Type 8619 English ...
Page 193: ......
Page 194: ...www burkert com ...