8311
3
ENGLISH
ENGLISH
type of
message
description
to do
10 ERR
The connection to the measuring cell
is interrupted.
Unplug the M12 power supply connector
Open the cover and check the connection between the measuring
cell and the electronic board.
If the message appears frequently, send the device back to your
Bürkert sales office.
Connection of the
measuring cell
6.3 a problem?
-
Protection code lost
(see parag. 5.4): press keys
0......9
simulta-
neously for 30 seconds when the display asks for your code, to access
the desired mode.
-
the display flashes
: The measuring range is exceeded.
-
«----» is displayed
: The limit values that can be displayed have been
exceeded. Choose an appropriate pressure unit.
-
the transmitter resets as soon as at least one transistor output
switches
: The line impedance is too high (see p. 11)