7.4.
electrical wiring
danger
Risk of injury due to electrical discharge
• Shut down and isolate the electrical power source before
carrying out work on the system.
• Observe all applicable accident protection and safety regula-
tions for electrical equipment.
note
• Use cables with an operating temperature limit suitable for your
application.
use a high quality electrical power supply (filtered and
regulated).
• Under normal conditions of use, cable with a cross section
of 0.75 mm
2
should be enough to transmit the signal.
• Do not install the cable near high voltage or high frequency
cables.
• If this is unavoidable, keep a minimum distance of 30 cm.
make sure the installation is equipotential (power supply
- 8012):
• Connect the different earth connections of the installation to
one another in order to remove any differences in potential
which may arise between two earth connections.
• Correctly connect the cable shielding to the earth.
• Connect the negative power supply terminal to the earth
to eradicate the effects of common mode currents. If this
connection cannot be made directly, a 100 nF/50 V capacitor
can be fitted between the negative power supply terminal
and the earth.
Power supply
+
-
(*)
12-36VDC
8012 with cable gland
+
-
(*)
12-36VDC
(**)
Power supply
8012 with m12 fixed
connector
*) If a direct earth connection is not possible, fit a 100 nF/50 V condenser
between the negative power supply terminal and the earth
**) If the cable used is shielded.