24
Adjustment and functionalities
DELT DELT
DELT
DELT
0
1
T° corresponding to a 4 mA input
current
Min. commutation range
Lower relay threshold (OLO)
Hysteresis (= 2x DELT)
Upper relay threshold (OHI)
Max. commutation range
T° corresponding to a 20 mA input current
Relay thresholds
external setpoint 4...20 mA
Fig. 18: Operational diagram of the 4...20 mA input
9.3.3.
Operational example of the 4...20 mA input
In the example in Fig. 19:
-
the commutation range is 0 °C...100 °C
-
the hysteresis is 20
-
DELT is equal to hysteresis/2 so DELT = 10 °C.
→
Calculating the temperature corresponding to an input current of 4 mA: Min. commutation range + DELT = 0 + 10 = 10 °C
→
Calculating the temperature corresponding to an input current of 20 mA: Max. commutation range - DELT = 100 − 10 = 90 °C
→
Set the transmitter parameters with the temperatures calculated (see chapter
).
english
Type 8400