Adjustment and functionalities
2 s
OHI
OLO
2 s
2 s
DEL = 0 s
DEL = 2 s
DEL = 0 s
DEL = 2 s
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
T°
Hysteresis mode
Not inverted
Inverted
Window mode
Time
Not inverted
Inverted
Not inverted
Inverted
Not inverted
Inverted
Fig. 26: Behaviour of the device according to the temperature
and the commutation mode selected
9.7.2.
Default configuration
When switching on for the first time, the Calibration mode con
-
figuration on 8400 threshold detectors and transmitters is as
follows:
T° unit
°C
Output
Hysteresis, inverted
OLO
130 °C / +266 °F
(threshold detectors and transmitters that
do not use the 4...20 mA input)
OHI
130 °C / +266 °F
(threshold detectors and transmitters that
do not use the 4...20 mA input)
DEL
0 s
Filter
2
BGLO
0 °C / +32 °F
BGHI
100 °C / +212 °F
Temperature
adjustment
000.0
Expansion board
•
no (NO EXT) for threshold detectors
•
yes (YES EXT) for transmitters
Output
english
Type 8400