21
Start-up with Bürkert Communicator
Type ME64
9.4.3
Configuration of input filter
For nominal operating mode “Frequency”, “Flow” or “Flow totaliser”.
To reduce signal fluctuations, one input filter with PT1 behaviour can be enabled per channel. The filter
response time can be set from 1 to 10,000 ms, but must be greater than the set sample time. Inputting 0 ms
deactivates the filter.
9.4.4
Configuration of flow input
For nominal operating mode “Flow” or “Flow totaliser”.
→
Enter K factor in [Pulses / Litre].
A 2-point calibration is subsequently possible under:
Digital inputs
>
Maintenance
>
Flow input calibration
.
9.4.5
Configuration of channel name
A user-specific name can be entered here for each channel.
9.4.6
Configuration of inversion
For inverting sensor signals in “Digital” nominal operating mode.
9.4.7
Configuration of wire break detection
For activating or deactivating a wire break detection in “Digital” nominal operating mode.
English