Servicing and maintenance
Type 8650 REV.2
fault
possible cause
CF LED is lit.
Wrong configuration.
→
Use the corresponding module from
the hardware catalogue.
Valve diagnostics responds
(short circuit, open output).
→
Check whether the valve is properly
installed.
→
Replace defective valves.
→
Disable diagnostics for unused valve
seats.
The module is not starting up due
to internal power limit
(short circuits in the outputs).
→
Remove short circuits (defective valves
at outputs).
→
Perform power reset of the module or
system.
If the ET 200iSP station (interface module IM 152) has started up with a profibus address X, the
address can be changed as follows (for details see
SIMATIC ET 200iSP operating instructions
):
→
Switch off the station.
→
Set the address 0 (all DIP switches in OFF position).
→
Switch on the station and wait approx. 10 seconds.
→
Switch off the station and then wait approx. 10 seconds.
→
Set the new, desired address Y.
→
Switch on the station.
The new address is adopted.
19.5
Repairs
If a repair is required, send the assembly to the responsible Bürkert branch or contact our Customer
Service.
Find the address and telephone number in chapter “5.1 Contact addresses” on page 14.