![Burkert 100 Nm Installation And Operation Manual Download Page 51](http://html1.mh-extra.com/html/burkert-0/100-nm/100-nm_installation-and-operation-manual_2832337051.webp)
3004 • Rev. 2109/06 • 00806090
51
EN
POSI-BBPR (GPS) : description
The GPS version includes BBPR and positioning function
.
Battery position backup:
This system insure a return to predefined position in case of power failure. The predefined position can be set close (default) or
open
.
Positioning:
0-10 V: In case of outside event, absence of control signal (accidental wires cut for example) but in the presence of power, the actua-
tor will travel to defined position (open or closed valve). As standard our actuators will close themselves with absence of control
signal but there are other possibilities on request.
4-20 mA: In case of outside event, absence of setpoint signal (accidental wires cut for example) but in presence of power, the actua-
tor will stay in its position
Actuator voltage
100 V to 240 V AC 50/60 Hz and 100 V to 350 V DC
20 V to 30 V AC 50/60 Hz and 20 V to 48 V DC
Battery voltage
24 V DC
Charging status feedback relay (65/66)
24 V DC - 1 A max
Battery capacity
600 mAh
Failure feedback relay (67/68)
24 V DC - 3 A max
Charging current
180 mA
Temperature
-10 °C à +40 °C
Maximum battery charge duration
3,5 h
II 2 G D Ex db IIB T6 Gb Ex tb IIIC T80 °C Db LCIE 07 ATEX 6078X / LCIE 22.0001X
Ambient temperature: -10 °C to +40 °C
C2
C4
LED
B1
B2
B3
C3
C1
C5
J1
C6
C7
C8
Rep
Terminals Description
B1
« Close » button
B2
« Mem» button
B3
« Open » button
C1
A,C
Motor connector
C2
67,68
Failure feedback relay
C3
65,66
Charging status feedback relay
C4
F (+)
F (-)
T (+)
Battery connector
C5
17 (-)
18 (+)
power supply connector
C6
15(-)
16(+)
Positioning setpoint signal con-
nector (0-10 V or 4-20 mA)
C7
13A(+)
13B(+)
14(-)
Positioning feedback signal con-
nector.
13A=0-10 V et 13B=4-20 mA
C8
A,0,B
RS485 connector
J1
CV1
Bluetooth
®
activation jumper
LED
Description
MANU manual / Bluetooth
®
functioning mode
ERROR
Error detected:
Timestamp memory empty/scheduler selected
Clock failure
Excessive temperature
Excessive torque
HORO Weekly scheduler functioning mode
ACT
Power supply:
Slow blinking (1 s) : charged battery
Rapid blinking (0.5 s) : battery charging
APPR Learning mode selected
APPR1
Open position stored (confirmation)
POSI
Positioning mode
APPR2
Closed position stored (confirmation)
The factory default configuration is "normally closed"