![Burkert 100 Nm Installation And Operation Manual Download Page 37](http://html1.mh-extra.com/html/burkert-0/100-nm/100-nm_installation-and-operation-manual_2832337037.webp)
3004 • Rev. 2109/06 • 00806090
37
EN
1)
Fuses for multivolt card :
- Card SNAA730100 : 5A / T 125V (Littelfuse 39615000000)
- Card SNAA730000 : 3,15A / T 250V (Multicomp MST 3,15A 250V)
2)
Possible defects : limitation of current, thermic limitation or program error
=> check that the valve torque is not superior to the maximum torque stand by the actuator
=> check that the actuator do not exceed the duty cycle indicated (possible overheat)
To re-start the actuator, reverse the sense of rotation or switch the power off and on.
SNAA730100
15 V - 30 V 50/60 Hz (12 V - 48 V DC)
SNAA730000
100 V - 240 V 50/60 Hz (100 V - 350 V DC)
A
B
G
A
B
E
F
D
C
C
C
C
E
F
D
G
Description
Description
A
Earth screw
E
2)
LED 3 : Detected failure
B
Pilot and power supply terminals
F
LED 1 : Power presence
C
1)
Card protection fuses
G
Failure report terminal strip (24V DC /
3A max)
D
LED 2 : microprocessor ok
Electronic boards