15
ChangesconcerningbüS/CANopendesign
5.2.4
Valve mode + Errors
The device status LED (Top LED) display the position feedback (S1, S2, S3) of the process valve and the
feedback S4IN from the external initiator as well as error messages.
The position feedback is displayed as shown below in “Tab. 5”.
If an
error
(i.e. internal error, bus error, error with teach or Autotune function, positions measuring sys tem signal
error) occurs, this is also displayed alternately according to the diagram: 1 second position feedback / 1 second
error display.
This display mode can be configured by software as of firmware revision B.02.00.00 (DIP 1 to 6: 111110) or can
be fixed using DIP switches (DIP 1 to 6: 101110) – see “Tab. 1”.
Position Process valve
position, e.g.:
Colour
Blinking pattern of the
position feedback
Fault indication
S1
closed
green
*)
continuously lit
is lit red alternating with colour from S1
S2
open
yellow
*)
continuously lit
is lit red alternating with colour from S2
S3
Cycle stroke
green
*)
continuously flashing slowly
**)
(250 ms ON, 250 ms OFF)
is lit red alternating with colour from S3
S4IN
ext. Initiator,
active
green
*)
continuously flashing quickly
**)
(125 ms ON,125 ms OFF)
is lit red alternating with colour from
S4IN
If there is no position feedback (S1 to S4IN), i.e. the process valve is in intermediate positions of the defined
teach points, the Top LED is off
*) ***)
.
Tab. 5:
Description of the colours and blinking patterns in “valve mode + errors” display mode
*)
Factory settings (other selectable colours for S1 to S4IN and also for the intermediate positions:
white, green, blue, yellow, orange, red, (Top) LED off)
**)
Factory settings (other selectable blinking patterns: [continuously lit], [125 ms ON + 125 ms OFF],
[250 ms ON + 250 ms OFF])
***)
Blinking pattern for the selected colour for the intermediate positions: continuously lit (alternating with pos-
sible error messages)
5.2.5
Valve mode + Warnings
The device status LED (Top LED) display the position feedback (S1, S2, S3) of the process valve and the
feedback S4IN from the external initiator as well as error and warning messages.
The position feedback is displayed as shown in “Tab. 6”.
If an
error or a warning
occurs (see colour assignment below “Tab. 6”), this is also displayed alternately:
1 second position feedback / 1 second error or warning display.
This display mode can be configured by software as of firmware revision B.02.00.00 (DIP 1 to 6: 111110) or can
be fixed using DIP switches (DIP 1 to 6: 110110) – see “Tab. 1”.