Power Cables
AC (20A)
Cable type
Connector type
2 per cabinet
3 x 4mm
/ AWG # 12 (US)
C22 Appliance Coupler
It is mandatory for power lines and terminal boxes to be located within the imme-
diate vicinity of the system and to be easily accessible. Each power line must be
connected to a separate, independent electrical panel and bipolar circuit breaker.
The PDU requires an extra cable length of 1.5 meters for connection inside the cabi-
net.
Electrical Specifications
(power supplies are auto–sensing and auto–ranging)
Current draw
Power consumption
Thermal dissipation
29.5 A max. at 200 VAC input
3000 VA per full CSS module)
1500 VA (per PDU)
2700 W / 9250 BTU (per full CSS module)
1300 W / 4610 BTU (per PDU
Europe
Nominal voltage
Voltage range
Frequency
230 VAC (Phase / Neutral)
207 – 244 VAC
50 Hz
1%
United States of America
Nominal voltage
Voltage range
Frequency
208 VAC (Phase / Neutral)
182 – 229 VAC
60 Hz
0.3%
Japan
Nominal voltage
Voltage range
Frequency
200 VAC (Phase / Neutral)
188 – 212 VAC
60 Hz
0.2%
Brazil
Nominal voltage
Voltage range
Frequency
220 VAC (Phase / Neutral)
212 – 231 VAC
60 Hz
2%
Breaker Protection
Mains power CSS module
Maximum inrush current
Mains power PDU
20A Curve C
210A / per quarter period
20A Curve C
Maximum inrush current
Mains power PDU
Maximum inrush current
210A / per quarter period
20A Curve C
210A / per quarter period
Table 37.
NovaScale 5080/5160 Server specifications
Summary of Contents for NovaScale 5000 Series
Page 1: ...Bull NovaScale 5000 Series User s Guide 86 A1 89EF 02 ORDER REFERENCE...
Page 2: ......
Page 20: ...xviii User s Guide...
Page 24: ...xxii User s Guide...
Page 56: ...2 14 User s Guide...
Page 98: ...4 30 User s Guide...
Page 150: ...5 52 User s Guide...
Page 176: ...User s Guide B 24...
Page 228: ...G 10 User s Guide...
Page 234: ...X 6 User s Guide...
Page 237: ......
Page 240: ......