Type FF-

Insulation test

The device is equipped with extensive EMC protection. If insulation tests are carried out the electronic filter devices will be dam-
aged. All necessary tests have been carried out for all concerned groups of components at the factory (test voltage 1 kV or 1.5 kV
respectively, depending on the device).

Moisture and broken-wire alarms are signaled via two independent dry contacts.

They are made fail-safe in the FF-HM and FF-19 types: The relays switch when power is turned on and no moisture is detected,
they fall off when power fails, moisture or a broken wire is detected. Relays are used in the opposite logic with the types FF-..-U
(switched in the alarm case).

The devices have three LEDs (FF-3-U-2: five LEDs) for POWER, BROKEN WIRE and MOISTURE.

Alarms are monostable; they switch back after the cause for the alarm is removed.

Using the FF-HM or FF-19 type a 

hold function

 can be chosen by setting/wiring a jumper. The alarm will stay until the internal or

externally connected reset button is pressed.

4.2.1 Controller type FF-19

Note the drawing 

47/075-06-4

.

This type can only be used with a 24 V DC power supply. 

NOTICE! The grounding to PE has always to be attached!

The detector FF-40 is connected to PIN 30 and 31, the shield to PIN 2.

Connect the cable to the FF-3-N. Root strands white and brown to PIN 30 and 31, and shielding to PIN 2.

For FF-3-N and FF-40 the jumper J2 is set to 2-3.

When using older models (FF-1) jumper J2 has to be set to 1-2. Otherwise the controller would signal a broken wire.

Alarm hold function:

To select this function, jumper J1 has to be set to 2-3. An external reset switch or contact can be connected to PIN 26 and 27 of the
bus connector.

NOTICE! When using a detector without broken wire-detection, the broken wire alarm is not used. The relay contact may then
be used to look for power supply failure.

When installing the FF-3-N or FF-40 detector, both relays are used. A power supply failure may be seen by combining both alarm
outputs with an AND function since in working condition EITHER moisture alarm OR broken wire alarm is given.

4.2.2 Controller type FF-HM

Note the drawing 

41/073-01-4

 and 

41/074-01-4

.

On the upper terminal are the connections for power supply and alarm relay outputs, on the lower terminal the moisture de-
tector and the external reset switch are connected.

The type FF-HM-230 is suitable for 230 V AC and 115 V AC. 

The jumpers are factory set to 230 V AC.

 To change it to 115 V AC discon-

nect the jumper between terminals 9-10 and set jumpers to terminals 8-9 and 10-11. The power supply is connected to terminals
12-13 (PE is 7).

The type FF-HM-24 is only suitable for 24 V DC. The power supply is connected to terminals 12-13. 

NOTICE! Even with this control-

ler, PE has always to be connected to terminal 7!

Connecting the moisture detector:

The detector FF-40 is connected to terminals 25-26, the shield to 24.

Connect the cable to the FF-3-N. Root strands white and brown to terminals 25-26, and shielding to terminal 24.

When using models FF-3-N and FF-40, terminals 22 and 23 stay open to ensure broken wire detection.

When using older models (FF-1), a jumper must be set between terminals 22 and 23.

Hold function:

To enable this function, a jumper has to be set between terminals 20 and 21. An external reset switch or contact may be connec-
ted to terminals 14 and 15. The shield of this wire is connected to terminal 16.

7

Bühler Technologies GmbH

BE410002 ◦ 09/2017

Summary of Contents for FF-1-U

Page 1: ...Original instructions Moisture detector controllers Type FF BE410002 09 2017 Bühler Technologies GmbH Harkortstr 29 D 40880 Ratingen Tel 49 0 21 02 49 89 0 Fax 49 0 21 02 49 89 20 E Mail analyse buehler technologies com Internet www buehler technologies com ...

Page 2: ... this instruction carefully prior to installation and or use Pay at tention particularly to all advises and safety instructions to prevent in juries Bühler Technologies can not be held responsible for misusing the product or unreliable function due to unauthorised modifications All rights reserved Bühler Technologies GmbH 2017 Document information Document No BE410002 Version 09 2017 ...

Page 3: ...4 1 2 Mounting of detector controller 6 4 2 Electrical connections 6 4 2 1 Controller type FF 19 7 4 2 2 Controller type FF HM 7 4 2 3 Controller type FF U 8 5 Operation and control 9 5 1 Adjusting the sensitivity 9 6 Maintenance 10 6 1 Replacement of fuses 10 7 Service and repair 11 7 1 Spare parts and accessories 11 7 2 Troubleshooting 11 8 Disposal 12 9 Appendices 13 9 1 Technical Data 13 9 2 D...

Page 4: ...lowcell in PVDF Type S flowcell in stainless steel Controllers Voltage Connectible moisture detectors FF HM 230 for rail mounting 230 115 V AC for one FF 3 N moisture detector or FF 40 FF HM 24 for rail mounting 24 V DC for one FF 3 N moisture detector or FF 40 FF 19 19 rack 24 V DC for one FF 3 N moisture detector or FF 40 FF 1 U inside small casing 230 115 V AC for one or two moisture detectors ...

Page 5: ...art of the equipment The manufacturer keeps the right to modify specifications without advanced notice Keep this manual for later use Signal words for warnings DANGER Signal word for an imminent danger with high risk resulting in severe injuries or death if not avoided WARNING Signal word for a hazardous situation with medium risk possibly resulting in severe injuries or death if not avoided CAUTI...

Page 6: ...e spare parts Always observe the applicable safety and operating regulations in the respective country of use when performing any type of maintenance DANGER Electrical voltage Electrocution hazard a Disconnect the device from power supply b Make sure that the equipment cannot be reconnected to mains unintentionally c The device must be opened by trained staff only d Regard correct mains voltage DA...

Page 7: ...the original case or in appropriate packing If the device is not used for some time protect it against heat and humidity Store the device in a roofed dry and dust free room Temperature should be between 20 C and 40 C 4 F and 104 F 5 Bühler Technologies GmbH BE410002 09 2017 ...

Page 8: ...atures in order to ensure the necessary tightness in the system 4 1 2 Mounting of detector controller Controller type FF 19 This type is designed as an insert for 19 housings The bus connector is a DIN 41612 type B Used pins of columns a and c are plated through Before inserting the FF 19 into the housing set the jumpers Controller types FF HM The type FF HM is designed for standard 35 mm rail mou...

Page 9: ... switch or contact can be connected to PIN 26 and 27 of the bus connector NOTICE When using a detector without broken wire detection the broken wire alarm is not used The relay contact may then be used to look for power supply failure When installing the FF 3 N or FF 40 detector both relays are used A power supply failure may be seen by combining both alarm outputs with an AND function since in wo...

Page 10: ...5 pin terminal X3 with the white and brown con ductors according to the connection diagram On protective element type FF 3 U the moisture detector attaches to the 3 pin ter minal X3 Connect the shielding with care The signal relay for Type FF 3 U and FF 1 U connect to the 6 pin terminal above the switch on Type FF 3 U 2 they connect to a 12 pin terminal Please also refer to the connection plans FF...

Page 11: ...and ER 145 A Ex sensitivity is reduced by turning the potentiometer counter clockwise Turn until the alarm turns off We recommend disabling the hold function during adjustment Otherwise the reset switch has to be pressed during the whole procedure At the FF U the setting of sensitivity is quite the same But first the enclosure must be opened The potentiometer is on the up per right next to the ter...

Page 12: ...nance against toxic corrosive gases Use suitable pro tective equipment The devices work free of maintenance In case of failure see the table in chapter Troubleshooting page 11 The controllers are internally fused by Ø5x20 fuses To replace the fuses turn off the power supply see chapter Troubleshooting page 11 The fuses have to be replaced by the same type The following fuses are used Controller ty...

Page 13: ...logies com 7 1 Spare parts and accessories Item no Description 41 11 100 FF 3 N moisture detector without cable 41 11 1000 FF 3 N moisture detector with cable 41 89 699 FF 40 moisture detector 40 11 000 Type G flowcell PVDF 40 11 000I Type NPT1 4 flowcell PVDF 40 11 005 Type S flowcell stainless steel 41 11 020 Controller FF HM 230 41 11 030 Controller FF HM 24 41 11 017 Controller FF 1 U 41 11 01...

Page 14: ...al Dispose of parts so as not to endanger the health or environment Follow the laws in the country of use for disposing of elec tronic components and devices during disposal 12 Bühler Technologies GmbH BE410002 09 2017 ...

Page 15: ...V AC 50 60 Hz 10 24 V DC 10 24 V DC 10 230 115 V AC 50 60 Hz 10 230 115 V AC 48 62 Hz 10 Max switching output current 230 V 2 A 24 V AC DC 2 A 24 V AC DC 2 A 230 V 2 A AC 250 V 5 A DC 150 V 5 A Protection class IP 40 Terminals IP 20 IP 40 Terminals IP 20 IP 20 when built in IP 65 IP 40 Terminals IP 20 Ex protection class II 1 G EEx ia Ga IIC Max lead length 4 m 4 m 4 m 4 m 70 m Dimensions WxHxD mm...

Page 16: ...45 A Ex 70 75 Housing depth 109 Housing depth 170 Power Reset Moisture alarm Cable break alarm Sensitivity controller Housing depth 81 94 180 Housing depth 120 22 5 99 Cable break Condensate 14 Bühler Technologies GmbH BE410002 09 2017 ...

Page 17: ... Connections diagrams 47 075 06 4 type FF 19 41 073 01 4 type FF HM 230 41 074 01 4 type FF HM 24 41 065 07 4 types FF U Declaration of Conformity KX410001 RMA Decontamination Statement 15 Bühler Technologies GmbH BE410002 09 2017 ...

Page 18: ......

Page 19: ......

Page 20: ......

Page 21: ......

Page 22: ......

Page 23: ...iften schreiben vor dass Sie uns diese Dekontaminierungserklärung ausgefüllt und unterschrieben zurücksenden müssen Bitte füllen Sie auch diese im Sinne der Gesundheit unserer Mitarbeiter vollständig aus This return form includes a decontamination statement The law requires you to submit this completed and signed decontamination statement to us Please complete the entire form also in the interest ...

Page 24: ...vice as specified above has been properly cleaned and decontaminated and that there are no risks present when dealing with the device Ansonsten ist die mögliche Gefährdung genauer zu beschreiben In other cases please describe the hazards in detail Aggregatzustand bitte ankreuzen Aggregate state please check Flüssig Liquid Fest Solid Pulvrig Powdery Gasförmig Gaseous Folgende Warnhinweise sind zu b...

Reviews: