DeNOx
9 Appendices
9.1 DeNOx technical Data
Gas Probe Technical Data
Operating temperature:
max. 280 °C
Operating pressure:
90 kPa…100 kPa
Regulator temperature range:
+50 to +280 °C
Ambient temperature:
-20 to +35 °C*
Electrical data:
230 V, 50 Hz, 3 A; approx. 700 W / 115 V, 60 Hz**
Degree of protection:
IP44
Parts in contact with mediums:
1.4571, glass, PVDF, Norprene, Viton, PTFE
*Please contact us for higher temperatures.
**115 V version available upon request.
Additional ambient conditions
relative humidity:
10 % ... 90 %
Height above sea level:
2000 m
Storage temperature:
-20 °C … 60 °C
Rel. storage humidity (not condensed)
20 % ... 80%
9.2 DeNOx Wiring diagram
Mainboard
SSR-Board
power supply add-on
power
Heater probe
status probe temperature
Pt100 heated adapter
Pt100 probe
power supply add-on
heated adapter
antifreeze heater, condensate pump
Fig. 1:
DeNOx wiring diagram
34
Bühler Technologies GmbH
BX460035 ◦ 08/2017