Conducting service work on the automated primary burner controller LMO
5
Buderus Blue Flame Burner BE 1.3 - 2.3 - Specifications subject to change without notice.
14
5.3
Repairing faults in the automated
burner controller LMO
After a fault shut off the burner, the LED on the automat-
ed burner controller LMO will light red. The faults can be
identified by observing a flash code.
Proceed as follows:
z
Press reset button for 5 seconds until the LED briefly
flashes yellow.
z
Observe the flash code and find the type of the fault
in the table (Table 8).
z
Press reset button for one second to stop the diagno-
sis and to unlock the burner.
Flash code
Possible cause
Correction
2 x flash
no flame formed during safety time
Troubleshooting (see Chapter 10 „Troubleshooting burner failures“,
page 39).
4 x flash
Stray light at burner start
7 x flash
Flame goes out during operation
8 x flash
oil pre-heater time monitoring
First check electrical connections.
Next step replace oil pre-heater.
10 x flash
Internal error
Unlock LMO
Wiring fault
(Press reset button for one second).
Next step, replace LMO.
LED "flickers"
RED
Interface mode is active
Activate interface diagnosis by pressing the reset button for five seconds.
If the diagnosis has been accidentally activated (LED "flickers" red), it can
be switched off by pressing the reset button again for five seconds. It sig-
nals the mode change by a yellow flash.
Table 8 Diagnosing faults
NOTICE
The control outputs are deactivated and
the burner remains off while diagnosing
faults.