44
We reserve the right to make any changes due to technical modifications.
Commissioning and maintenance instructions Logano GE434 Gas-fired special boiler • Issue 02/2003
Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
Heating system inspection and maintenance
8
Confirm maintenance
!
Sign the maintenance report in this manual.
Boiler size
Rated gas nozzle pressure
Natural gas
H (G 20)
L (G 25)
S (G 25.1)
GZ50
mbar
150 - 375
14
Tab. 14 Rated gas nozzle pressure
Boiler
size
Nozzle pressure
LPG
Propane
P (G 31)
Supply pressure
(Flow pressure)
58 - 37
36
35
34
33
32
31
30
29
28
27
kW
mbar
mbar
mbar
mbar
mbar
mbar
mbar
mbar
mbar
mbar
mbar
150 - 375
35
34
33
32
31
30
29
28
27
26
25
Tab. 15 Nozzle pressure for LPG P subject to the supply pressure
Boiler
size
Nozzle pressure
LPG
Butane/propane mixtures
B/P (G 30)
Supply pressure
(Flow pressure)
58 - 37
36
35
34
33
32
31
30
29
28
27
kW
mbar
mbar
mbar
mbar
mbar
mbar
mbar
mbar
mbar
mbar
mbar
150 - 375
31.5
31.5
31.5
31.5
31
30
29
28
27
26
25
Tab. 16 Nozzle pressure for LPG B/P subject to the supply pressure