Technical Information
3
Logano G125 BE - Specifications subject to change without notice.
11
3.2.5 Requirements for Power Supply
3.2.6 Conditions Pertaining to Piping and Water Quality
Operating Conditions
Comments – Detailed Information
Main power supply
120 V
Provide proper grounding for equipment and personal protection.
High amp protection
10 A
Frequency
60 Hz
Protection
–
Group all equipment per local code
Table 7 Power supply
Operating Conditions
Comments – Detailed Information
Operating pressure (over pres-
sure)
12 – 58 psi
Maximum pressure is 30 psi based on supplied relief valve
Allowable test pressure
45 – 75 psi
Adjustable temperature limit
TR
122 – 194 °F
Manual reset high limit
210 °F
In combination with Beckett AquaSmart the limit value (210 °F) may not be excee-
ded.
Water quality
–
Initial fill water and make-up water should be potable water type quality. A pH
range of 8.2 to 9.5 is desired.
Table 8 Piping and water quality