3
Failures / Errors
GB012 - 25K
19
3A
is flashing.
Fan sensor not detected.
(This failure only occurs if there is a sensor or the cable physical defect)
Control Step
Action
1.
Is th fan cables damaged ?
yes:
B
Switch off the appliance.
B
Change the cables.
B
Switch on the appliance.
3A failure still exist ? -->2.
no:
-->2.
2.
Is there any problem at fan sensor
and cable ?
B
Switch off the appliance.
B
Check the sensor and cable.
yes:
B
Change the cable and sensor.
B
Switch on the appliance.
3A failure still exist ? -->3.
no:
-->3.
3.
Electronic card is defect.
B
Switch off the appliance.
B
Cut mains supply.
B
Change the electronic card.
B
Connect to main supply.
B
Switch on the appliance.