7
Boiler installation
Logano GC 144 II – 6 720 808 893 (2017/02)
8
7.2
Connecting the heating system
Fig. 8
Low-water cut-off installation
[1]
Boiler
[2]
Radiator
[3]
Heating system with low-water cut-of
[4]
Heating system without low-water cut-off
NOTICE:
Boiler damage due to moisture.
▶ Protect the components of the gas ignition system
from moisture (dripping, spray, rain) during
installation of the boiler, during operation and during
maintenance work (such as replacing the pump,
replacing the control, etc.).
NOTICE:
System damage due to overheating as a result
of a low water condition.
▶ Note that a boiler installed above the level of the
heating system must be equipped with a low-water
cut-off. The low-water cut-off must be installed
during installation of the boiler and placed above the
water level in the boiler without any means of
shutting the water off between the boiler and low
water cut-off
(
NOTICE:
System damage due to high temperature
variations in the heating system.
▶ If the boiler is operated in connection with a
refrigeration system, make sure that the pipes for the
refrigerated liquid are connected in parallel to the
boiler system with suitable valves to prevent the
refrigerated liquid from entering the boiler.
▶ The piping system of a boiler connected to the
heating coils of hydro-air heating systems that may
be exposed to the circulation of cooled air must be
equipped with a flow-control valve or some other
automatic system for preventing the boiler water
from circulating by gravity during the cooling cycle.
1
2
2
1
2
2
2
2
3
4
6 720
8
04 440-0
8
.2T