5
Cleaning and maintenance
Logano G201 - Subject to technical modifications.
18
5.1.1
Frequent cleaning
The ashes must be removed from the combustion cham-
ber/ash pan every 1 to 3 days.
V
Open the ash pan door [2].
V
Fold the front grate downwards and remove the seg-
ment plate (
Æ
Fig. 6, page 13 and Fig. 7, page 13).
V
Tip the combustion residues into the ash pan.
V
Insert the segment plate and fold the front grate
upwards.
V
Remove the combustion residues from the ash pan
with the ash shovel [1].
Fig. 14 Cleaning the ash pan
1
Ash shovel
2
Ash pan door
5.1.2
Monthly cleaning
The heat exchanger heater flue and the flue gas header
(
Æ
Fig. 16, page 19) must be checked monthly and
cleaned if necessary. Insufficient cleaning can cause
damage to the boiler and the voiding of warranty claims.
Heat exchanger heater flue, cleaning
V
Open the fuel fill door [2] and remove the waste steam
plate [1].
V
Clean the ash residues from the heat exchanger with
brushes.
Do not bump against the back wall in order to avoid
damage and leaks.
V
Insert the waste steam plate [1] and close the fuel filler
door [2].
V
Take the steps described under 5.1.1.
Fig. 15 Heat exchanger heater flue, cleaning
1
Waste steam plate
2
Fuel filler door
Do not place hot ashes in plastic and waste
containers.
WARNING:
Risk of system damage due to
insufficient maintenance and cleaning!
V
Clean the heat exchanger heat flues and
the flue gas header regularly.