Servicing
5
40
Installation and servicing instructions condensing gas boiler 800 - 24/29/43/60 and 800 - 24T25/29T25 H/V • edition 02/2006
Subject to modifications resulting from technical improvements !
Buderus • http://buderus-domestic.co.uk
Code
Meaning
4F
Flow sensor exceeds 100 °C
Possible
cause
Action
1
Resistance in the installation is too high
Check if (thermostatic) radiator valves are clogged with dirt
2
Boiler capacity is too large for the installation
Adjust the boiler’s capacity
3
Safety sensor is faulty
Check the sensor and measure if resistance over the
sensor is correct. If not replace safety sensor
(see subsection 5.3.9 and subsection 5.3.10)
4
Problem with the pump or pump cabling
(no circulation)
Check if the pump cabling is faulty or if the pump is stuck
(see subsection 5.3.7)
5
Water pressure is too low in the installation
Top up the system (see subsection 2.1.1)
Code
Meaning
4L
Short circuit in safety sensor
Possible
cause
Action
1
Safety sensor is faulty
Check the sensor and measure if resistance over the
sensor is correct. If not replace safety sensor
(see subsection 5.3.9 and subsection 5.3.10)
2
A short or bad connection in the cable harness
Check the cable harness and/or connector of the sensor
3
UBA might be faulty
Check the UBA by temporarily connecting a different UBA
(see subsection 5.3.5)
Code
Meaning
4P
Safety sensor has a loose connection or is defective
Possible
cause
Action
1
Safety sensor faulty or disconnected
Check the sensor and measure if resistance over the
sensor is correct. If not replace safety sensor
(see subsection 5.3.9 and subsection 5.3.10)
2
A short or bad connection in the cable harness
Check the cable harness and/or connector of the sensor
(see subsection 5.3.12)
3
UBA might be faulty
Check the UBA by temporarily connecting a different UBA
(see subsection 5.3.5)
Code
Meaning
4U
Short circuit in flow sensor
Possible
cause
Action
1
Flow sensor is dirty or faulty
Check the sensor, replace if necessary
(see subsection 5.3.9 and subsection 5.3.10)
2
A short or bad connection in the cable harness
Check the cable harness and/or connector of the sensor
(see subsection 5.3.12)