Users manual Buderus 800 - 24/29/43/60 and 800 - 24T25/29T25 H/V • Edition 02/2006

Subject to modifications resulting from technical improvements !

 Buderus Ltd. • http://www.buderus-domestic.co.uk

6

Commissioning

6.1

Preparing the boiler for operation

Note the operating instructions of the control unit.

z

Open the control panel cover.

z

Check the water pressure (fig. 1, item 3).
If the pressure is below 1.0 bar, top up water and 
purge air from the system. 
Max. water pressure 2.0 bar.
If water is lost frequently, have a specialist company 
look for and eliminate the cause.

z

Adjust the flow temperature on the controller 
(fig. 1, item 1) using table 1.

z

Adjust the hot water temperature on the controller 
(fig. 1, item 2) using table 2.

z

Use the control unit or remote control unit to set 
the room temperature to maximum.

z

Open the gas service valve: push in and turn to the 
left in vertical position (fig. 1, item 4).

z

Turn the mains switch (fig. 1, item 5) into position "

I

". 

The boiler runs through the start-up program and the 
burner is ignited after approx. 30 seconds.

z

Close the control panel cover.

z

Use the control unit or remote control unit to adjust 
the room temperature to the desired value.

Fig. 1

Control panel, pressure display, gas service valve

Tab. 1

Flow water temperature

* Basic setting: the actual flow water temperature is determined by the digital control system. 

Have specific system settings adjusted on the digital control system by the specialist heating system company.

Tab. 2

Hot water temperature

1

2

10

1

0

1

11

KW

10

1

10

1

I

0

1

2

3

4

5

Control unit

Application

Controller position / flow temperature

Digital Room Controller 

i

RT

HW4201, RC

Floor heating
Radiator heating

1

(40

°

C)* 

8

(80

°

C, factory setting)*

ON/OFF temperature controller, 24 V

Floor heating
Radiator heating

1

(40

°

C) 

6

(40 °C, new building) up to

8

(80 °C, old building)

Application

Controller

position

Hot water temperature of external reservoirs

Minor convenience, small heat losses

1

27

°

C

Average convenience, medium heat losses

5

40

°

C

Optimum convenience, normal heat losses

10

60

°

C

Summary of Contents for 800 - 24

Page 1: ...7212 3700 02 2006 GB EN For the user Please read thoroughly before operating the unit Users manual Gas wall hung Boiler condensing Buderus 800 24 29 43 60 and Buderus 800 24T25 29T25 H V...

Page 2: ...tallation and Use Regulations The Building Regulations current I E E Wiring Regulations and the relevant British Standard Codes of Practice The device may only be used in combination with the units ac...

Page 3: ...ammable materials or liquids near the heating boiler I NOTE To prevent the boiler from being damaged care must be taken not to contaminate the combustion air with halogenated hydrocarbons e g containe...

Page 4: ...ns switch fig 1 item 5 into position I The boiler runs through the start up program and the burner is ignited after approx 30 seconds z Close the control panel cover z Use the control unit or remote c...

Page 5: ...Move the mechanical switch on the three way valve to centre position fig 2 applicable for 24T25 and 29T25 only and systems with an external storage type water heater z Connect temporary hose of the fi...

Page 6: ...three start up trials 7 Shutting down the boiler z Open the control panel cover z Turn the mains switch fig 6 item 1 into position 0 z Close the gas service valve by turning it to the right fig 6 ite...

Page 7: ...5 H V Edition 02 2006 7 Subject to modifications resulting from technical improvements Buderus Ltd http www buderus domestic co uk z Place hose on the draining tule z Turn to drain the system Fig 6 Ma...

Page 8: ...buderus domestic co uk Buderus is a trading name of BBT Thermotechnology UK Ltd Customer Services Technical Product Support Sales Returns Spares Tel 0870 421 5933 Tel 0870 421 5944 Tel 01905 752 640 T...

Reviews: