background image

Grounding conductor

 is not required for connection at the 

BTR

 Control Units.

Connection optical smoke detector (VdS-testet)

COM -

LED -

IN +

Grounding
conductor
Shielding

C

onneCtion

 o

ptiCal

 S

moke

 D

eteCtor

 

IN

OUT

COM

IN

OUT

COM

IN

OUT

COM

BCR

+

+

+

-

-

IN+

OUT+

COM-

10 k

IN+

OUT+

COM-

IN+

OUT+

COM-

+

+

EL 72

EL 6000

X2

X2

+

-

17 18

4 5

1 2

9000032201_V0.1_KW26/20

www.btr-hamburg.de

♦ 

BTR

 GmbH 

 

♦ 

Gemeindewald 11 

 D-86672 Thierhaupten 

 

♦ 

Telefon: +49 8271 811 92-0 

 Fax: +49 8271 811 92-55 

LED display

Display

State

red

 lights 

- continuous

alarm triggered

red

 blinks

- 1x per second

test mode

yellow

 blinks - every 4 seconds

fault

yellow

 blinks - 1x per second

quiescent value adjustment
Degree of contamination: 75 %

Important note for detector test:

If the voltage of the detector line is interrupted by 
disconnecting and connecting or by pressing the 
reset button in the control unit, the detectors react 4 
minutes later to the checking with testing gas.
The test mode is indicated by a red blinking of the 
LED-display.
A yellow blinking every 4 seconds indicates a detector 
fault (if necessary, replace detector).

Connection  

smoke detector 

Part.-No.: 60.300

Connect 10 k

Ω 

resistor at terminals 

+

 / 

-

 of unused detector lines!

               A 15   resistor must be used  
          

   when connecting to the 

EL6000

!

Insert 10 k

 termination resistor  

in the last or only detector.

OUT +

ø 5,5

(2x)

ø 72

!

Reviews: