58
2 Installation
2.8
Power cable connection
The indicative height of cable connections (from the floor) for every type of QMT module with
entrance from below is described in the following table.
Module
H Height from
the floor (mm)
CCST
590
(1)
DS1/DLM
940
(1)
DL/DS
380
(2)
BM1
500
BMC/BMR
500
(1)
This module is preset for the con-
nection of 2 cables
(max section 240 mm²) for pole.
(2)
This module is preset for the con-
nection of 1 cable
(max section 70 mm²) for pole
A
B
A
A
A
A
CCST
DS1/DLM/DS
BM1
BMC/BMR
DL
Standard LV compartment for auxiliary
circuits.
Dim. = W375-750xH450xD330mm
A
B
LV compartment for ICBV and ILCBV
module with standard
protection relay: functions 50-51-51N.
Dim. = W375xH250xD270mm
Internal arc proof series on 4 sides 16kA
x 1s