background image

2

ST-00000220-

24/04/2019

K4659

EN

Settings

Sensor parameters

Default value

Adjustable parameters

Configuration remote control

BMSO4001

BMSO4003

Time delay

15 mn

3,5,10,15,20 mn

30s - 255 h 59 mn 59s

Sensitivity

PIR (very high)

Low, medium, high, very high

Brightness threshold

300 lux

20, 100, 300, 500, 1000 lux

0 - 1275 lux

Oper

ating

mode

Auto

Not active

ON/OFF

Walkthrough

ON

ON/OFF

Eco

Not active

ON/OFF

Det

ec

tion 

mode

Initial

PIR

Cannot be modified

Holding

PIR

Cannot be modified

Retrigger

PIR

PIR/OFF

Alarm

Not active

ON/OFF

Adv

anc

ed 

mode

Calibration

0 - 99995 lux

Adjustment

Not active

ON/OFF

Contribution of light

Automatic

Automatic - 1275 lux

 Time  delay 

The period of time after which the load is switched off if no movement is detected.

The time restarts whenever the sensor detects a movement. 

 Sensitivity 

Adjustment of the sensitivity of the detection technology used.

 Brightness  threshold 

Lighting level below which the sensor activates the load and above which it 

switches it off.

Operating mode:

 Auto

The load is automatically switched on:

- upon detection of a movement if the level of natural light is insufficient. 

The load is automatically switched off:

- if no movement is detected at the end of the set time delay + standby time.

- or if the level of natural light is insufficient (adjustment on).

Each new detection causes automatic switching on if the light is insufficient.

 Walkthrough

If a movement is detected for a time of less than 20 s, the sensor will decrease 

the set time delay to 3 minutes. If the set delay time set is already less than three 

minutes, it will remain as such.

 Eco

The load is switched on manually while switching off is automatic:

- if no movement is detected at the end of the set delay time.

After switching off the load, if any movement is detected within 30 s, the load is 

automatically switched back on (retrigger function on). At the end of this time

interval, the load must be switched back on manually.

Detection mode

Set of technologies used for detection.

Initial:

 set of technologies used for the first detection.

Holding:

 set of technologies used after the first detection.

Retrigger: 

set of technologies used for the Retrigger function.

After switching off, any new detection within 30 seconds will cause the load to switch 

back on automatically. After 30 seconds, the load must be switched back on manually. 

Available only in Eco mode.

Alarm: 

before switching off the load the sensor emits an audible warning signal. 

Intervals: 1 minute, 30 seconds, and 10 seconds.

Advanced mode:

 

Calibration

To calibrate the sensor, it is necessary to measure the lighting level present using 

a lux meter and send the value to the sensor using a configuration remote control 

(BMSO4001). 

Calibration procedure:

Step 1: with only artificial light.

Switch the load on at maximum intensity and close the shutters (if you cannot do 

this then wait for sunset).

Measure the level of lighting and send it to the sensor via the remote control.

Step 2: with only natural light.

Turn off the load and open the shutters.

 

Adjustment 

This function allows the sensor to switch off the load 10 minutes (plus a safety 

threshold to avoid inappropriate switching off) after the lighting level exceeds the 

brightness threshold, even though movement has been detected.

Contribution of light: 

amount of supplementary light supplied by switching on the 

load.

When the contribution of light parameter is set to “auto” the sensor automatically 

calculates the contribution of light.

PIR flush mounting motion sensor

Summary of Contents for Living Now BMS04001

Page 1: ... threshold 20 to 1275 LUX Positioning the detector Description Voltage 27Vdc Maximum current draw 15 mA Connection between sensor and actuator SCS BUS connector Sensor type PIR movement detector with 180 detection angle and brightness sensor Flush mounted box depth 40 mm Weight 60 g Impact resistance IK04 Penetration of solids and liquids IP20 Time delay 5 sec 59min 59 sec Brightness 20 1275 lux O...

Page 2: ...f is automatic if no movement is detected at the end of the set delay time After switching off the load if any movement is detected within 30 s the load is automatically switched back on retrigger function on At the end of this time interval the load must be switched back on manually Detection mode Set of technologies used for detection Initial set of technologies used for the first detection Hold...

Page 3: ...ecific manual 1 Lighting Management System Modification of the parameters using the configuration remote controls Configuration Volume coverage 8 m PIR 5 m PIR 3 m PIR 6 m PIR 1 2 m m 6 4 5 8 Small movements Large movements For further configurations use the remote control item BMS04001 BMS04003 see www legrandoc com ON OFF Auto function factory setting The sensor parameters are defined by 6 confi...

Page 4: ...tness level depending on the configurator on D For example when the brightness of the natural light increases the sensor reduces the brightness of the light unit controlled For appropriate operation the brightness sensitivity threshold of the sensor must be configuredusingtheDconfigurator Thethresholdvaluecanbemodifiedusingabrightnesscontrol Thenewvalueisthenconfiguredasthenewsensor threshold unti...

Page 5: ...ensesclean Cleanthesurfacewithacloth Donotuse acetone detergentsforremovingtar ortrichloroethylene Maintenanceusingthefollowingproducts Hexane En60669 1 Methylatedspirit Soapywater Dilutedammonia Bleach diluted10 Glassdetergents BUS EN PIR flush mounting motion sensor ...