Height
Performance
1,2 m
m
6
4
5
8
8 m (PIR)
5 m (PIR)
3 m
(PIR)
≈ 6 m
(PIR)
Modification of the parameters by the configuration tools
• BMSO4001 :
Advanced configuration tool
• BMSO4003 :
Simplified configuration tool
When the detector receives an IR command via a configuration tool, it emits a beep
confirming that the modification has been taken into account.
Return to factory settings:
1
st
press: Short press on LEARN, the LED flashes slowly.
2
nd
press: Press and hold down LEARN for 10 seconds until the LED flashes quickly.
Detection system:
Initial detection:
The load is switched on as soon as the first detection occurs if the
natural light level is below the light level threshold.
Maintain:
The load remains active if another presence is detected.
Light level parameters:
Light level threshold:
Value at which the load comes on if the light level is
below the setting and goes off if it is above this threshold.
Advanced mode:
Calibration:
The surrounding light level measured with a luxmeter must then be
transmitted to the detector.
Retrigger:
In manual mode.
Function allowing automatic switch-on of the product
after a period of 30 seconds following the load being switched off.
After it has been switched off, another detection within a 30-second period triggers
automatic switch-on.
After more than 30 seconds the device must be switched on manually.
Alarm:
An audible signal is emitted before the device is switched off (1 minute,
30 seconds and 10 seconds before switch-off).
Light regulation:
Automatic switch-off of the load 10 minutes after the light
level threshold is exceeded combined with an additional safety threshold (to
avoid unintended switch-off).
Provision of light:
Quantity of additional lux provided by the load being
switched on.
Sensor parameters
Default value
Modifiable parameters
Configuration tools
BMSO4001
BMSO4003
Light level threshold
300 lux initially
Tripper position
20, 100, 300, 500, 1000 lux
−
0 - 1275 lux
−
Ad
vanced mode
Calibration
−
0 - 99995 lux
−
Light regulation
Inactive
Activate/Deactivate
−
Provision of light
Auto
Auto - 1275 lux
−