background image

3

1,2 m

m

6

4

5

8

8 m (PIR/US)

5 m (PIR/US)

3 m

(PIR/

US)

≈ 6 m 

(PIR/

US)

067226 HD/HC/HS4658

L/N/NT4658N

574048

574098 AM5658

Height

Performance

• BMSO4001 - 088230:

 advanced configuration remote control

• BMSO4003 -088235:

 simplified configuration remote control

When the sensor receives an IR command from a configuration remote control, it
beeps to confirm that the modification has been acquired.
For more information on the parameters please refer to the technical info sheet of the 
remote control BMSO4001.

Restoring the factory settings:

1

st

  press: Briefly press LEARN, the LED will blink slowly.

2

nd

  press: Press and hold LEARN for 10 seconds until the LED flashes quickly.

Small movements

Large movements

PIR+US flush-mounted SCS Green Switch

MQ00473-f-EN

09/06/2014

If a movement is detected for a time of less than 20 s, the sensor will decrease 

the set time delay to 3 minutes. If the set delay time set is already less than three 

minutes, it will remain as such.

Eco

The load is switched on manually while switching off is automatic:

- if no movement is detected at the end of the set delay time.

After switching off the load, if any movement is detected within 30 s, the load is 

automatically switched back on (retrigger function on). At the end of this time 

interval, the load must be switched back on manually.

Detection mode

Set of technologies used for detection.

Initial:

 set of technologies used for the first detection.

Holding: 

set of technologies used after the first detection.

Retrigger:

 set of technologies used for the Retrigger function.

After switching off, any new detection within 30 seconds will cause the load to switch 

back on automatically. After 30 seconds, the load must be switched back on manually. 

Available only in Eco mode.

Alarm:

 before switching off the load the sensor emits an audible warning signal. 

Intervals: 1 minute, 30 seconds, and 10 seconds.

Advanced mode:

Calibration

To calibrate the sensor, it is necessary to measure the lighting level present using 
a lux meter and send the value to the sensor using a configuration remote control 
(BMSO4001). 
Calibration procedure:
Step 1: with only artificial light.
Switch the load on at maximum intensity and close the shutters (if you cannot do 
this then wait for sunset).
Measure the level of lighting and send it to the sensor via the remote control.
Step 2: with only natural light.
Turn off the load and open the shutters.

Adjustment

 

This function allows the sensor to switch off the load 10 minutes (plus a safety 
threshold to avoid inappropriate switching off) after the lighting level exceeds the 
brightness threshold, even though movement has been detected.

Contribution of light:

 amount of supplementary light supplied by switching on the 

load.
When the contribution of light parameter is set to "auto" the sensor automatically 
calculates the contribution of light.

Modification of the parameters using the configuration remote controls

Reviews: