Commissioning and Maintenance 

 

The installation and commissioning must be done by qualified personnel only. Before energising the KLC 
flame  detector  please  check  the  cable  and  wiring  connections  are  in  accordance  to  the  diagram  and 
instructions given above. For good maintenance which will ensure trouble free operation of the KLC flame 
detector; please keep the sight glass clean by wiping with a soft dry clean cloth. Warning: Do not use any 
kind of cleaning sprays or fluids. 
During commissioning and after any cleaning maintenance, the flame detector should be checked, as the 
UV  tube  is  subject  to  a  natural  ageing  process  and  towards  the  end  of  its  life  span  it  is  prone  to 
malfunction.  To  check  that  the  flame  detector  is  sound  we  recommend  the  following  procedures  be 
followed:- 

 

Start  the  burner  with  the  fuel  supply  closed-off  or  remove  the  flame  detector  from  its  mounting 
flange and cover the UV tube using a soft cloth to avoid touching the glass lens.  The control box 
will lock-out at the end of the safety time due to absence of a flame signal. 

 

Remove  the  flame  detector  from  its mounting  flange.    Start  the  burner  while  exposing  the  flame 
detector to an external UV radiation source such as a cigarette lighter flame, or a small gas flame 
(n.b. electric room lighting or a torch is inadequate).  The burner Control Box must go to lock-out 
due to detecting an extraneous light source either immediately or at the end of the air pre-purge 
cycle, depending on the type/model of the Control Box.  

 

Close off the fuel supply or remove flame detector from its mounting flange and cover the UV tube 
using a soft cloth when the burner is in the "run" position.  The control box must go immediately to 
lock-out resulting in the burner shutting down. 

 

If  any  of  these  safety  checks  do  not  function  as  described  i.e.  they  should  always  result  in  burner 
shutdown and control box lock-out; then it is essential to replace the flame detector with a new KLC flame 
detector. For safety  and trouble free burner operation, we recommend that the flame detector should be 
replaced  after  every  10,000  hours  of  burner  operation  or  approximately  every  30months  for  a  burner 
operating on an average of 10 hours per day.  

 
 

 