11
To stop (
“
”
), press the “
3~Bal
1~
” and “
HOLD
” buttons at the same time again.
Annunciator “ ” turns off. The
kWHr Recording
result is then displayed on the LCD
for immediate viewing. Annunciator “ ” turns on & flashes.
When the low battery annunciator
“
” turns on, the meter will stop (
“
”
)
kWHr
recording
session automatically and display
kWHr Recording
result as in above.
Note:
During
kWHr Recording
session, real-time
W
,
VAR
,
VA
as well as
kWHr
accumulated readings can be selected by pressing the
SELECT
button momentarily. A
flashing “ ” denotes that
kWHr Recording
is still under-going. An always on “ ”
denotes that
kWHr Recording
is being paused.
When
kWHr Recording
is not activated,
kWHr
stored result instead of accumulated
readings is displayed when selected as in above. Annunciator “ ” turns on & flashes.
The meter separately stores one Single-Phase and one 3-Phase-Balanced-Load
kWHr
result for later viewing. When they are being viewed, press “
3~Bal
1~
” button
momentarily to toggle between them.
When the display readings exceed 9999kWHr/999hours, exponential readings are
displayed. “2.3E4” kWHr represents 2.3 x 10
4
kWHr, or 23000 kWHr for example,.
After the
kWHr Recording
session is stopped (
“
”
) properly, the new result will
supersede the previous one stored in the non-volatile memory. You can then switch off
the meter for transportation, storage, or even battery changing with memory remained.
To avoid mis-storage to memory, it is important to properly stop (
“
”
)
kWHr
Recording
session before sliding the slide-switch function-selector to any other
function positions.
3-Phase 3-Wire (3
3W) Unbalanced-Load Power Function
Set the slide-switch function-selector to the “
3~Un-Bal
” Power position. Press
“
3W 4W
” button momentarily to select 3-Wire measurements. Annunciator “
3W
” turns
on.
Clamp the jaws around “Line 1” as reminded by annunciators “
L1
”, and connect
Black test probe (
COM
terminal) to “Line 3” and Red test probe (
+
terminal) to “Line 1”
as reminded by annunciators “
” on mini-display.
When the reading is stable, press “
” button momentarily to enter the first
measuring value.
Then clamp the jaws around “Line 2” as reminded by annunciators “
L2
”, and
connect Black test probe (
COM
terminal) to “Line 3” and Red test probe (
+
terminal) to
“Line 2” as reminded by annunciators “
” on mini-display.