26
Advanced Settings
These options customize how long each stage will run before the next
stage turns on. You may also program when a particular stage is turned
on based on the temperature delta between the set temperature and the
current temperature.
d
Reverse Staging
If enabled, the thermostat will cycle down from
the higher stages so that when it approaches set point it will only
be running in stage 1. The thermostat calculates which stage to
start the HVAC equipment in depending on the indoor tempera-
ture and set point temperature delta. The HVAC equipment will
start in stage 1. As the stage 1 temperature delta is exceeded, the
second stage will engage. Once the equipment has brought the
current temperature back to within the heat or cool differential
setting, stage 2 will disengage and stage 1 will remain running
until the set point is met.
d
Stage 2 Temp Delta
The minimum difference between the cur-
rent temperature and the set temperature that will activate the
auxiliary heat (regardless if the maximum run time of the previ-
ous stage was reached). Options are Auto (default) and 1 to 10
°
F
(0.6 to 5.6
°
C).
d
Stage 1 Max Runtime
The maximum amount of time stage 1
will run before engaging the next stage. Options are Auto (de-
fault) and 10 to 120 minutes.
d
Comp to Aux Runtime
The maximum amount of time this stage
will run before engaging the next stage. Options are Auto (de-
fault) and 1 to 10
°
F (0.6 to 5.6
°
C).
d
Comp to Aux Temp Delta
The minimum difference between the
current temperature and the set temperature that will activate this
stage (regardless if the maximum run time of the previous stage
was reached). Options are Auto (default), Disabled, and 1 to 10
°
F (0.6 to 5.6
°
C).
d
Cool Min On Time
Sets the minimum equipment run time in
cool mode: 1 to 20 min (default is 5 min).
d
Heat Min On Time
Sets the minimum equipment run time in
heat mode: 1 to 20 min (default is 5 min).