2. C is used to connect the brown wire of the thermostat to
provide a return path to ground through the fuse which
protects the transformer. C is fused on the HK61GA001
board.
3. G is used to control the switching of the relay to turn the fan
on through the normally open contact of the relay.
4. Y on the HK61GA001 is used as the junction for the
outdoor section’s Y connection which controls the compres-
sor contactor for heat pump and cooling modes. The
HK61GA003 board contains a 90-sec fan-off delay which
begins timing when the Y is de-energized.
5. O is used as a junction for a heat pump reversing valve
circuit.