Bryant PURON 533A Installation And Start-Up Instructions Manual Download Page 4

recommendations in the Application Guideline and Service
Manual—Air Conditioners and Heat Pumps Using Puron® Refrig-
erant will reduce these losses. Refer to Table 1 for field tubing
equivalent line length. Refer to Table 2 for accessory require-
ments.

No buried-line applications greater than 36 in.

If refrigerant tubes or indoor coil are exposed to atmosphere, they
must be evacuated to 500 microns to eliminate contamination and
moisture in the system.

A.

Outdoor Unit Connected to Factory-Approved

Indoor Unit

Outdoor unit contains correct system refrigerant charge for opera-
tion with ARI rated indoor unit with highest sales volume when
connected by 15 ft of field-supplied or factory-accessory tubing.
Check refrigerant charge for maximum efficiency.

B.

Install Liquid-Line Filter Drier

CAUTION:

Installation of filter drier in liquid line is

required.

Refer to Fig. 6 and install filter drier as follows:

1. Braze 5-in. connector tube to liquid service valve. Wrap

filter drier with damp cloth.

2. Braze filter drier between connector tube and liquid tube to

indoor coil. Flow arrow must point towards indoor coil.

C.

Refrigerant Tubing

Connect vapor tube to fitting on outdoor unit vapor service valves.
Connect liquid tube to filter drier. (See Fig. 6 and Table 1.) Use
refrigerant grade tubing.

D.

Sweat Connection

CAUTION:

To avoid valve damage while brazing, ser-

vice valves must be wrapped in a heat-sink material such
as a wet cloth.

Service valves are closed from factory and ready for brazing. After
wrapping service valve and filter drier with a wet cloth, braze
sweat connections using industry accepted methods and materials.
Consult local code requirements. Refrigerant tubing and indoor
coil are now ready for leak testing. This check should include all
field and factory joints.

E.

Evacuate Refrigerant Tubing and Indoor Coil

CAUTION:

Never use the system compressor as a

vacuum pump.

Refrigerant tubes and indoor coil should be evacuated using the
recommended deep vacuum method of 500 microns. The alternate
triple evacuation method may be used if the procedure outlined
below is followed. Always break a vacuum with dry nitrogen.

DEEP VACUUM METHOD

The deep vacuum method requires a vacuum pump capable of
pulling a vacuum of 500 microns and a vacuum gage capable of
accurately measuring this vacuum depth. The deep vacuum
method is the most positive way of assuring a system is free of air
and liquid water. (See Fig. 7.)

TRIPLE EVACUATION METHOD

The triple evacuation method should be used when vacuum pump
is only capable of pumping down to 28 in. of mercury vacuum and
system does not contain any liquid water. Refer to Fig. 8 and
proceed as follows:

1. Pump system down to 28 in. of mercury and allow pump to

continue operating for an additional 15 minutes.

2. Close service valves and shut off vacuum pump.

3. Connect a dry nitrogen cylinder and regulator to system and

open until system pressure is 2 psig.

4. Close service valve and allow system to stand for 1 hr.

During this time, dry nitrogen will be able to diffuse
throughout the system absorbing moisture.

5. Repeat this procedure as indicated in Fig. 8. System will

then be free of any contaminants and water vapor.

IMPORTANT:

Check to be certain factory tubing on both indoor

and outdoor unit has not shifted during shipment. Ensure tubes are
not rubbing against each other or any sheet metal. Pay close
attention to feeder tubes, making sure wire ties on feeder tubes are
secure and tight.

VIII.

MAKE ELECTRICAL CONNECTIONS

WARNING:

To avoid personal injury or death, do not

supply power to unit with compressor terminal box cover
removed.

Be sure field wiring complies with local and national fire, safety,
and electrical codes, and voltage to system is within limits shown
on unit rating plate. Contact local power company for correction of
improper voltage. See unit rating plate for recommended circuit
protection device.

NOTE:

Operation of unit on improper line voltage constitutes

abuse and could affect unit reliability. See unit rating plate. Do not
install unit in system where voltage may fluctuate above or below
permissible limits.

NOTE:

Use copper wire only between disconnect switch and

unit.

NOTE:

Install branch circuit disconnect of adequate size per

NEC to handle unit starting current. Locate disconnect within sight
from and readily accessible from unit, per Section 440-14 of NEC.

A.

Route Ground and Power Wires

Remove access panel to gain access to unit wiring. Extend wires
from disconnect through power wiring hole provided and into unit
control box.

Fig. 5—Position of Sensing Bulb

A81032

2  O'CLOCK

10  O'CLOCK

SENSING  BULB

STRAP

SUCTION  TUBE

8  O'CLOCK

4  O'CLOCK

7

8

 IN. OD &  SMALLER

LARGER  THAN 

 

7

8

 IN. OD

 

—4—

Summary of Contents for PURON 533A

Page 1: ...ipment or components on Puron equipment INSTALLATION RECOMMENDATIONS NOTE In some cases noise in the living area has been traced to gas pulsations from improper installation of equipment 1 Locate unit...

Page 2: ...and the maximum outdoor operating ambient in cooling mode is 125 F V CHECK INDOOR CHECK FLO RATER PISTON AND INSTALL PISTON RING 533A STANDARD If unit is to be installed with a piston metering device...

Page 3: ...to tubing or valve to attach TXV to distributor 9 Reinstall TXV support clamp removed in item 3 10 Attach TXV bulb to vapor tube inside cabinet in same location as original was when removed using sup...

Page 4: ...icrons and a vacuum gage capable of accurately measuring this vacuum depth The deep vacuum method is the most positive way of assuring a system is free of air and liquid water See Fig 7 TRIPLE EVACUAT...

Page 5: ...ensure terminations are secured properly Check wire routing to ensure wires are not in contact with tubing sheet metal etc IX COMPRESSOR CRANKCASE HEATER When equipped with a crankcase heater furnish...

Page 6: ...ONS AND RECOMMENDED LIQUID LINE AND VAPOR TUBE DIAMETERS IN UNIT SIZE LIQUID VAPOR VAPOR LONG LINE Connection Diameter Tube Diameter Connection Diameter Tube Diameter Connection Diameter Tube Diameter...

Page 7: ...6 To obtain required subcooling temperature at a specific liquid line pressure add refrigerant if liquid line tempera ture is higher than indicated or reclaim refrigerant if temperature is lower Allo...

Page 8: ...and covers 2 Tighten service valve stem caps to 1 12 turn past finger tight 3 Leave User s Manual with owner Explain system operation and periodic maintenance requirements outlined in manual 4 Fill o...

Page 9: ...55 57 59 10 45 47 49 51 53 55 57 59 61 12 47 49 51 53 55 57 59 61 63 14 49 51 53 55 57 59 61 63 65 16 51 53 55 57 59 61 63 65 67 18 53 55 57 59 61 63 65 67 69 20 55 57 59 61 63 65 67 69 71 22 57 59 6...

Page 10: ...IR CONDITIONER C INDOOR FAN HEAT STAGE 1 COOL STAGE 1 C SEE NOTE 2 G A97367 24 VAC HOT 24 VAC COM R C G W W1 Y Y2 R C C BRYANT NON PROGRAMMABLE THERMOSTAT MODEL AC FA FB FC FD FF FAN COIL AIR CONDITIO...

Page 11: ...THERMOSTAT FK4C FAN COIL AIR CONDITIONER C INDOOR FAN HEAT STAGE 1 COOL STAGE 1 Y1 C SEE NOTE 2 G O J1 JUMPER J2 JUMPER A97365 Fig 11 Typical 24v Circuit Connections Cont 24 VAC HOT R G W W1 Y Y2 O W2...

Page 12: ...actory approved liquid line filter drier is required on every unit Do not use an R 22 TXV If indoor unit is equipped with an R 22 TXV it must be changed to a Puron TXV Never open system to atmosphere...

Reviews: