Bryant PURON 533A Installation And Start-Up Instructions Manual Download Page 3

INSTALLING TXV IN PLACE OF PISTON

1. Pump system down to 2 psig and recover refrigerant.

2. Remove hex nut from piston body. Use backup wrench on

fan coils.

3. Remove and discard factory-installed piston. Be sure Teflon

seal is in place.

4. Reinstall hex nut. Finger tighten nut plus 1/2 turn.

NOTE:

If the piston is not removed from the body, TXV will not

function properly.

CAUTION:

To prevent damage to the unit, use a brazing

shield and wrap TXV with wet cloth or use heat sink
material.

5. Install TXV on indoor coil liquid line. Sweat swivel adapter

to inlet of indoor coil and attach to TXV outlet. Use backup
wrench to avoid damage to tubing or valve. Sweat inlet of
TXV, marked “IN” to liquid line. Avoid excessive heat
which could damage valve.

6. Install vapor elbow with equalizer adapter to suction tube of

line set and suction connection to indoor coil. Adapter has
a 1/4-in. male connector for attaching equalizer tube.

7. Connect equalizer tube of TXV to 1/4-in. equalizer fitting

on vapor line adapter.

8. Attach TXV bulb to horizontal section of suction line using

clamps provided. Insulate bulb with field-supplied insula-
tion tape. See Fig. 5 for correct positioning of sensing bulb.

9. Proceed with remainder of unit installation.

REPLACING TXV ON R-22 INDOOR COIL

1. Pump system down to 2 psig and recover refrigerant.

2. Remove coil access panel and fitting panel from front of

cabinet.

3. Remove TXV support clamp using a 5/16-in. nut driver.

Save the clamp.

4. Remove R-22 TXV using a backup wrench on flare

connections to prevent damage to tubing.

5. Using wire cutters, cut equalizer tube off flush with vapor

tube inside cabinet.

6. Remove bulb from vapor tube inside cabinet.

IMPORTANT:

Route the equalizer tube of Puron® TXV through

suction line connection opening in fitting panel prior to replacing
fitting panel around tubing.

7. Braze equalizer stub-tube closed. Use protective barrier as

necessary to prevent damage to drain pan.

8. Install TXV with 3/8-in. copper tubing through small hole

in service panel. Use wrench and backup wrench, to avoid
damage to tubing or valve, to attach TXV to distributor.

9. Reinstall TXV support clamp (removed in item 3).

10. Attach TXV bulb to vapor tube inside cabinet, in same

location as original was when removed, using supplied bulb
clamps (nylon or copper). See Fig. 5 for correct positioning
of sensing bulb.

11. Route equalizer tube through suction connection opening

(large hole) in fitting panel and install fitting panel in place.

12. Sweat inlet of TXV, marked

IN

to liquid line. Avoid

excessive heat which could damage valve.

13. Install vapor elbow with equalizer adapter to vapor line of

line set and vapor connection to indoor coil. Adapter has a
1/4-in. male connector for attaching equalizer tube.

14. Connect equalizer tube of TXV to 1/4-in. equalizer fitting

on vapor line adapter. Use backup wrench to prevent
damage to equalizer fitting.

15. Proceed with remainder of unit installation.

CAUTION:

Remove indoor coil piston if unit is to be

installed on system with a TXV metering device.

VII.

MAKING PIPING CONNECTIONS

WARNING:

Relieve pressure and recover all refrigerant

before system repair or final unit disposal to avoid
personal injury or death. Use all service ports and open all
flow-control devices, including solenoid valves.

CAUTION:

Do not leave system open to atmosphere

any longer than minimum required for installation. POE
oil in compressor is extremely susceptible to moisture
absorption. Always keep ends of tubing sealed during
installation.

CAUTION:

If ANY refrigerant tubing is buried, provide

a 6 in. vertical rise at service valve. Refrigerant tubing
lengths up to 36 in. may be buried without further special
consideration. Do not bury lines over 36 in.

CAUTION:

To prevent damage to unit or service valves

observe the following:
• Use a brazing shield
• Wrap service valves with wet cloth or use a heat sink
material.

Outdoor units may be connected to indoor section using accessory
tubing package or field-supplied refrigerant grade tubing of correct
size and condition. For tubing requirements beyond 50 ft, substan-
tial capacity and performance losses can occur. Following the

Fig. 4—Check-Flo-Rater® Components (533A Use)

A01164

PISTON

TEFLON SEAL

PISTON RETAINER

13

16

–IN.

BRASS HEX
NUT

3

4

–IN. BRASS

HEX BODY

STRAINER

DISTRIBUTOR

COPPER TUBE

PISTON
RING

—3—

Summary of Contents for PURON 533A

Page 1: ...ipment or components on Puron equipment INSTALLATION RECOMMENDATIONS NOTE In some cases noise in the living area has been traced to gas pulsations from improper installation of equipment 1 Locate unit...

Page 2: ...and the maximum outdoor operating ambient in cooling mode is 125 F V CHECK INDOOR CHECK FLO RATER PISTON AND INSTALL PISTON RING 533A STANDARD If unit is to be installed with a piston metering device...

Page 3: ...to tubing or valve to attach TXV to distributor 9 Reinstall TXV support clamp removed in item 3 10 Attach TXV bulb to vapor tube inside cabinet in same location as original was when removed using sup...

Page 4: ...icrons and a vacuum gage capable of accurately measuring this vacuum depth The deep vacuum method is the most positive way of assuring a system is free of air and liquid water See Fig 7 TRIPLE EVACUAT...

Page 5: ...ensure terminations are secured properly Check wire routing to ensure wires are not in contact with tubing sheet metal etc IX COMPRESSOR CRANKCASE HEATER When equipped with a crankcase heater furnish...

Page 6: ...ONS AND RECOMMENDED LIQUID LINE AND VAPOR TUBE DIAMETERS IN UNIT SIZE LIQUID VAPOR VAPOR LONG LINE Connection Diameter Tube Diameter Connection Diameter Tube Diameter Connection Diameter Tube Diameter...

Page 7: ...6 To obtain required subcooling temperature at a specific liquid line pressure add refrigerant if liquid line tempera ture is higher than indicated or reclaim refrigerant if temperature is lower Allo...

Page 8: ...and covers 2 Tighten service valve stem caps to 1 12 turn past finger tight 3 Leave User s Manual with owner Explain system operation and periodic maintenance requirements outlined in manual 4 Fill o...

Page 9: ...55 57 59 10 45 47 49 51 53 55 57 59 61 12 47 49 51 53 55 57 59 61 63 14 49 51 53 55 57 59 61 63 65 16 51 53 55 57 59 61 63 65 67 18 53 55 57 59 61 63 65 67 69 20 55 57 59 61 63 65 67 69 71 22 57 59 6...

Page 10: ...IR CONDITIONER C INDOOR FAN HEAT STAGE 1 COOL STAGE 1 C SEE NOTE 2 G A97367 24 VAC HOT 24 VAC COM R C G W W1 Y Y2 R C C BRYANT NON PROGRAMMABLE THERMOSTAT MODEL AC FA FB FC FD FF FAN COIL AIR CONDITIO...

Page 11: ...THERMOSTAT FK4C FAN COIL AIR CONDITIONER C INDOOR FAN HEAT STAGE 1 COOL STAGE 1 Y1 C SEE NOTE 2 G O J1 JUMPER J2 JUMPER A97365 Fig 11 Typical 24v Circuit Connections Cont 24 VAC HOT R G W W1 Y Y2 O W2...

Page 12: ...actory approved liquid line filter drier is required on every unit Do not use an R 22 TXV If indoor unit is equipped with an R 22 TXV it must be changed to a Puron TXV Never open system to atmosphere...

Reviews: