8
2. Remove horizontal (metal) ductcovers to access vertical
(downflow) discharge duct knockouts in unit basepan. (See
Fig. 9.)
NOTE
: These panels are held in place with tabs similar to an
electrical knockout. Reinstall horizontal duct covers (Fig. 9)
shipped on unit from factory. Insure openings are air and
watertight.
NOTE
: The design and installation of the duct system must be in
accordance with the standards of the NFPA for installation of
nonresidence--type air conditioning and ventilating systems, NFPA
90A or residence--type, NFPA 90B; and/or local codes and
ordinances.
Adhere to the following criteria when selecting, sizing, and
installing the duct system:
1. Units are shipped for side shot installation.
2. Select and size ductwork, supply--air registers, and
return--air grilles according to American Society of Heating,
Refrigeration and Air Conditioning Engineers (ASHRAE)
recommendations.
3. Use flexible transition between rigid ductwork and unit to
prevent transmission of vibration. The transition may be
screwed or bolted to duct flanges. Use suitable gaskets to
ensure weather--tight and airtight seal.
4. All units must have field--supplied filters or accessory filter
rack installed in the return--air side of the unit.
Recommended sizes for filters are shown in Table 1.
5. Size all ductwork for maximum required airflow (either
heating or cooling) for unit being installed. Avoid abrupt
duct size increases or decreases or performance may be
affected.
6. Adequately insulate and weatherproof all ductwork located
outdoors. Insulate ducts passing through unconditioned
space, and use vapor barrier in accordance with latest issue
of Sheet Metal and Air Conditioning Contractors National
Association (SMACNA) and Air Conditioning Contractors
of America (ACCA) minimum installation standards for
heating and air conditioning systems. Secure all ducts to
building structure.
7. Flash, weatherproof, and vibration--isolate all openings in
building structure in accordance with local codes and good
building practices.
Horizontal Duct Covers
A09061
Basepan
Downflow
(Vertical)
Supply
Knockout
Basepan
Downflow
(Vertical)
Return
Knockout
A09088
Fig. 9 -- Supply and Return Duct Opening
Step 8 — Install Electrical Connections
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death.
The unit cabinet must have an uninterrupted, unbroken
electrical ground to minimize the possibility of personal
injury if an electrical fault should occur. This ground may
consist of an electrical wire connected to the unit ground
screw in the control compartment, or conduit approved for
electrical ground when installed in accordance with NFPA
70 (NEC) (latest edition) (in Canada, Canadian Electrical
Code CSA C22.1) and local electrical codes.
!
WARNING
704D
--
--
A
Summary of Contents for Legacy 704D--A
Page 3: ...3 A09467 Fig 2 704D A24 36 Unit Dimensions 704D A...
Page 4: ...4 A09468 Fig 3 704D A42 60 Unit Dimensions 704D A...
Page 17: ...17 A10202C Fig 13 Connection Wiring Diagram 208 230 3 60 704D A...
Page 18: ...18 A10202L Fig 13 Cont Ladder Wiring Diagram 208 230 3 60 704D A...
Page 21: ...21 A08490 Fig 15 Cooling Charging Chart 704D A...
Page 41: ...41 A10201 Fig 41 Connection Wiring Diagram 230 3 704D A...
Page 42: ...42 A10201 Fig 41 Cont Ladder Wiring Diagram 230 3 704D A...
Page 43: ...43 A10203 Fig 42 Connection Wiring Diagram 460 3 704D A...
Page 44: ...44 A10203 Fig 42 Cont Ladder Wiring Diagram 460 3 704D A...