GUIDE SPECIFICATIONS

GENERAL

System Description

Outdoor--mounted, air--cooled, split--system heat pump unit

suitable for ground or rooftop installation. Unit consists of a

hermetic compressor, an air--cooled coil, propeller--type

condenser fan, and a control box. Unit will discharge supply

air upward as shown on contract drawings. Unit will be used in

a refrigeration circuit to match up to a packaged fan coil or coil

unit.

Quality Assurance

— Unit will be rated in accordance with the latest edition

of ARI Standard 240.

— Unit will be certified for capacity and efficiency, and

listed in the latest ARI directory.

— Unit construction will comply with latest edition of

ANSI/ ASHRAE and with NEC.

— Unit will be constructed in accordance with UL

standards and will carry the UL label of approval.

Unit will have C--UL approval.

— Unit cabinet will be capable of withstanding Federal

Test Method Standard No. 141 (Method 6061) 500--hr

salt spray test.

— Air--cooled condenser coils will be leak tested at 217

psig and pressure tested at 450 psig.

— Unit constructed in ISO9001 approved facility.

Delivery, Storage, and Handling

— Unit will be shipped as single package only and is

stored

and

handled

per

unit

manufacturer’s

recommendations.

Warranty (for inclusion by specifying engineer)

— U.S. and Canada only.

PRODUCTS

Equipment

— Factory assembled, single piece, air--cooled heat

pump unit. Contained within the unit enclosure is all

factory

wiring,

piping,

controls,

compressor,

refrigerant charge (R--22), and special features

required prior to field start--up.

Unit Cabinet

— Unit cabinet will be constructed of galvanized steel,

bonderized, and coated with a powder coat paint.

Fans

— Condenser fan will be direct--drive propeller type,

discharging air upward.

AIR--COOLED, SPLIT--SYSTEM HEAT PUMP

213R

1--1/2 TO 5 NOMINAL TONS

— Condenser fan motors will be totally enclosed,

1--phase type with class B insulation and permanently

lubricated bearings.

— Shafts will be corrosion resistant.
— Fan blades will be statically and dynamically

balanced.

— Condenser fan openings will be equipped with steel

wire safety guards.

Compressor

— Compressor will be hermetically sealed.
— Compressor will be mounted on rubber vibration

isolators.

Condenser Coil

— Condenser coil will be air cooled.
— Coil will be constructed of aluminum fins

mechanically bonded to copper tubes which are then

cleaned, dehydrated, and sealed.

Refrigeration Components

— Refrigeration

circuit

components

will

include

liquid--line shutoff valve with sweat connections,

vapor--line shutoff valve with sweat connections,

system charge of refrigerant, compressor oil,

accumulator, loss of charge switch, and reversing

valve.

Operating Characteristics

— The capacity of the unit will meet or exceed _____

Btuh at a suction temperature of _____

_

F. The power

consumption at full load will not exceed _____ kW.

— Combination of the unit and the evaporator or fan coil

unit will have a total net cooling capacity of _____

Btuh or greater at conditions of _____ CFM entering
air temperature at the evaporator at _____

_

F wet bulb

and _____

_

F dry bulb, and air entering the unit at

_____

_

F.

— The system will have a SEER of _____ Btuh/watt or

greater at DOE conditions.

Electrical Requirements

— Nominal unit electrical characteristics will be _____ v,

single phase, 60 hz. The unit will be capable of

satisfactory operation within voltage limits of _____ v

to _____ v.

— Nominal unit electrical characteristics will be _____ v,

three phase, 60 hz. The unit will be capable of

satisfactory operation within voltage limits of _____ v

to _____ v.

— Unit electrical power will be single point connection.
— Control circuit will be 24v.

Special Features

— Refer to section of this literature identifying

accessories and descriptions for specific features and

available enhancements.

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

E

Bryant Heating & Cooling Systems 7310 W. Morris St. Indianapolis, IN 46231

Printed in U.S.A.

Edition Date: 03/06

Replaces: PDS 213R.18.2

Catalog No. PDS 213R.18.3

Summary of Contents for LEGACY 213R

Page 1: ...sor S Filter drier S Loss of charge pressure switch S Balanced refrigeration system for maximum reliability Durability DuraGuardt protection package S Solid Durable sheet metal construction S Wire coi...

Page 2: ...ling Systems has determined that this product meets the ENERGY STAR guidelines for energy efficiency Refer to the combination ratings in Product Data for system combinations that meet Energy Star guid...

Page 3: ...ations for reliable system operation The maximum allowable total equivalent length is 250 ft The maximum vertical separation is 200 ft when outdoor unit is above indoor unit and 60 ft when the outdoor...

Page 4: ...sion kit is a 24 vac accessory that can turn a 4 wire thermostat application into a 5 wire application This kit can also be used to replace a broken thermostat wire or add an extra wire when needed Th...

Page 5: ...applications 5 Cycle Protector The cycle protector is designed to prevent compressor short cycling This control provides an approximate 5 minute delay after power to the compressor has been interrupte...

Page 6: ...low the second stage set point Usage Guideline Outdoor thermostat applications where electric heater is capable of 3 stage operation 14 Sound Hood Wraparound sound reducing cover for the compressor Re...

Page 7: ...10 AWG or smaller stranded wire for larger than 10 AWG is used consult applicable tables of the NEC ANSI NFPA 70 Length shown is as measured 1 way along wire path between unit and service panel for vo...

Page 8: ...8 DIMENSIONS NOTE Optional G dense coil guard shown 213R...

Page 9: ...BUILDING HEAT LOSS UNIT INTEGRATED HEATING CAPACITY MBTUH 0 0 2 9 5 9 8 8 11 7 14 6 17 6 20 5 23 4 kW 213RN A G 024A FA4CNF024 213RN A G 030A FA4CNF030 213RN A G 036A FC4DNF036 A05007 213RN A G 042A...

Page 10: ...A 17 300 TDR TXV 14 00 12 00 15 600 3 84 9 900 2 52 8 5 355AAV042060 CNRH 2417A 17 400 TDR TXV 14 00 12 00 15 600 3 82 9 900 2 52 8 5 355AAV042080 CNRH 2417A 17 400 TDR TXV 14 00 12 00 15 600 3 84 9 9...

Page 11: ...V 14 00 11 70 20 600 3 60 13 700 2 52 8 4 355AAV060100 CNRH 3017A 22 800 TDR TXV 14 00 11 70 20 600 3 60 13 700 2 50 8 2 355AAV060120 CNRH 3017A 22 800 TDR TXV 14 00 11 70 20 600 3 60 13 700 2 50 8 2...

Page 12: ...J AV036070 CNRV 3017A 28 600 TXV 13 00 10 50 29 600 3 44 18 900 2 44 8 1 CNRV 3017A 28 400 TDR TXV 14 00 11 50 29 200 3 52 18 000 2 50 8 2 355AAV042060 CNRV 3017A 28 400 TDR TXV 14 00 11 50 29 200 3 5...

Page 13: ...4 355AAV060120 CSRH 3612A 28 600 TDR TXV 14 00 11 50 28 800 3 62 18 100 2 54 8 4 315 A J AV036070 CSRH 3612A 28 600 TDR TXV 14 00 11 70 28 800 3 64 18 000 2 56 8 5 315 A J AV048090 CSRH 3612A 28 600 T...

Page 14: ...20 11 00 35 000 3 50 21 000 2 46 8 2 355AAV042040 CSRH 3612A 33 400 TDR TXV 13 50 11 20 34 800 3 52 20 800 2 48 8 2 355AAV042060 CSRH 3612A 33 400 TDR TXV 13 20 11 00 35 000 3 48 21 000 2 44 8 1 355A...

Page 15: ...4 00 11 50 41 000 3 64 25 400 2 58 8 1 315 A J AV060110 CNRV 4824A 42 000 TXV 13 00 10 80 42 500 3 58 26 400 2 48 7 9 CNRV 4824A 41 500 TDR TXV 13 50 11 20 41 500 3 56 25 600 2 52 7 9 355AAV042040 CNR...

Page 16: ...00 3 30 29 400 2 52 8 2 FK4DNB006 47 000 TDR TXV 14 00 11 50 47 500 3 42 29 400 2 58 8 4 CAR 4817A 43 500 TDR TXV 13 00 10 80 46 500 3 24 29 800 2 46 8 1 315 A J AV048090 CAR 4821A 44 500 TDR TXV 13 0...

Page 17: ...5AAV060100 CSRH 6012A 46 000 TDR TXV 13 50 11 20 47 500 3 26 29 600 2 50 8 1 355AAV060120 CSRH 6012A 46 000 TDR TXV 13 50 11 20 47 500 3 28 29 600 2 50 8 2 315 A J AV048090 CSRH 6012A 46 000 TDR TXV 1...

Page 18: ...4 1 67 14 42 14 42 1 86 13 76 13 76 2 06 675 72 20 63 11 24 1 25 19 87 10 95 1 39 19 07 10 66 1 54 18 23 10 35 1 71 17 35 10 04 1 90 16 43 9 70 2 11 67 18 77 14 41 1 25 18 05 14 11 1 38 17 28 13 79 1...

Page 19: ...0 94 FK4DNF002 1 03 0 95 FK4DNF003 1 03 0 95 CAR 2414A 1 01 1 01 CAR 2417A 1 01 1 01 CAR 3014A 1 01 1 01 CAR 3017A 1 01 1 01 CNRF 2418A 1 01 1 01 CNRH 2417A 1 01 1 01 CNRH 3017A 1 01 1 01 CNRV 2414A 1...

Page 20: ...1 01 1 04 CAR 3621A 1 01 1 04 CNRF 3618A 1 01 1 04 CNRH 3017A 1 01 1 04 CNRH 3617A 1 01 1 04 CNRV 3014A 1 01 1 04 CNRV 3017A 1 01 1 04 CNRV 3617A 1 01 1 04 CNRV 3621A 1 01 1 04 CSRH 3012A 1 01 1 04 CS...

Page 21: ...AV036070 CNRH 4221A 0 99 0 99 315 A J AV036070 CSRH 3612A 0 98 0 98 315 A J AV036070 CSRH 4212A 0 98 0 98 315 A J AV036070 CAR 3617A 0 98 0 98 315 A J AV048090 CNRH 3617A 0 98 0 98 315 A J AV048090 C...

Page 22: ...315 A J AV036070 CSRH 4212A 0 98 0 96 315 A J AV036070 CSRH 4812A 1 00 0 98 315 A J AV036070 CAR 4817A 1 00 0 98 315 A J AV048090 CNRH 4221A 0 98 0 96 315 A J AV048090 CNRH 4821A 1 00 0 98 315 A J AV0...

Page 23: ...8 46 38 46 5 60 57 46 72 46 72 3 34 45 23 45 23 3 71 43 67 43 67 4 12 42 02 42 02 4 57 40 29 40 29 5 06 38 47 38 47 5 60 Cooling Indoor Model Capacity Power Furnace Model FC4DN F B 048 1 00 1 00 FC4DN...

Page 24: ...5 5 53 63 10 35 87 6 05 60 01 34 75 6 61 56 79 33 60 7 21 67 65 44 49 83 4 58 62 86 48 76 5 00 60 20 47 66 5 46 57 46 46 53 5 97 54 61 45 35 6 52 51 65 44 13 7 13 63 60 91 48 02 4 53 58 49 46 94 4 95...

Page 25: ...17 40 17 40 1 50 16 62 16 62 1 48 15 45 15 45 1 45 75 525 9 19 8 45 1 37 11 68 10 73 1 44 14 53 13 25 1 51 17 67 15 70 1 60 19 47 17 72 1 65 19 53 19 53 1 65 19 14 19 14 1 63 18 57 18 57 1 61 600 9 3...

Page 26: ...7A 0 87 0 93 CNRF 2418A 1 00 0 96 CNRH 2417A 1 00 0 96 CNRH 3017A 0 87 0 93 CNRV 2414A 1 00 0 96 CNRV 2417A 1 00 0 96 CNRV 3014A 0 87 0 93 CNRV 3017A 0 87 0 93 CSRH 2412A 0 97 0 96 CSRH 3012A 0 85 0 9...

Page 27: ...98 0 98 CNRV 3017A 0 98 0 98 CNRV 3617A 0 97 0 97 CNRV 3621A 0 97 0 97 CSRH 3012A 0 98 0 98 CSRH 3612A 0 96 0 95 CAR 3014A 0 97 0 95 315 A J AV036070 CAR 3614A 0 97 0 94 315 A J AV036070 CNRH 3017A 0...

Page 28: ...97 315 A J AV036070 CAR 3617A 1 00 1 01 315 A J AV048090 CNRH 3617A 1 00 1 02 315 A J AV048090 CNRH 4221A 0 99 0 98 315 A J AV048090 CNRV 3617A 1 00 1 02 315 A J AV048090 CSRH 3612A 0 99 0 97 315 A J...

Page 29: ...A 0 99 0 99 315 A J AV048090 CNRH 4221A 0 96 0 99 315 A J AV048090 CNRH 4821A 0 98 0 98 315 A J AV048090 CSRH 4212A 0 98 0 98 315 A J AV048090 CSRH 4812A 0 99 0 99 315 A J AV048090 CAR 4221A 0 98 1 01...

Page 30: ...43 63 79 63 79 4 64 Heating Indoor Model Capacity Power Furnace Model FC4DN F B 048 1 00 1 00 FC4DN F B 048 1 01 1 01 FC4DN F B 060 1 01 0 99 FK4DNB006 0 99 0 98 FK4DNF005 0 99 1 02 CAR 4817A 0 97 1...

Page 31: ...0 5 07 2250 25 67 23 62 4 22 31 26 28 73 4 35 37 37 34 07 4 51 44 05 39 12 4 67 51 64 46 99 4 83 58 08 58 08 4 98 60 16 60 16 5 02 57 77 57 77 4 95 75 1750 24 36 22 41 4 27 30 00 27 57 4 45 36 07 32 8...

Page 32: ...n resistant Fan blades will be statically and dynamically balanced Condenser fan openings will be equipped with steel wire safety guards Compressor Compressor will be hermetically sealed Compressor wi...