background image

3

Remote Sensor Averaging

Typically, one Remote Room Sensor is used per zone, but multiple

sensors may be used and averaged in some applications. Averaging
requires a special series--parallel wiring method with a specific

number of sensors. See Fig. 2 in this manual for wiring diagram.

Sensor 1

Sensor 2

Sensor 3

Sensor 4

Damper Control

Module

ZS_

Damper Control

Module

ZS_C

A03233

Fig. 2 -- Remote Room Sensor -- Parallel Wiring

Smart Sensor

Any zone may use a Smart Sensor. It provides a temperature

display and buttons to adjust the desired temperature in that zone
only. It also displays outdoor temperature and indoor humidity

sensed at the User Interface. Only one Smart Sensor may be used
per zone. They cannot be averaged like Remote Room Sensors. If a

Smart Sensor is used in a zone, a Remote Room Sensor may also

be used in the same zone. The Remote Room Sensor has priority
over the Smart Sensor. The Smart Sensor will display the Remote

Room Sensor temperature.

NOTE

: Smart Sensors must be addressed to identify which zone it

will control. See Smart Sensor Installation Instructions for details.

Wiring Considerations

Ordinary thermostat wire is recommended. Use 22 AWG or larger

for normal wiring applications. Continuous wire lengths over 100
ft. should use 20 AWG or larger.

NOTE

: ABCD bus wiring only requires a four--wire connection;

however, it is good practice to run thermostat cable having more
than four wires in the event of a damaged or broken wire during
installation.
Each communicating device in the Evolution Zone System has a

four--pin connector labeled ABCD. It is recommended that the

following color code be used when wiring each device:
A — Green = Data A

B — Yellow = Data B
C — White = 24VAC (Com)

D — Red = 24VAC (Hot)
It is not mandatory that the above color code be used, but each
ABCD connector in the system MUST be wired consistently.

Locating Damper Control Module

All wiring is run back to the Damper Control Module. Select a
location near the furnace or fan coil where wiring from the User

Interface, each Remote Room Sensor or Smart Sensor, each

damper actuator, and the equipment itself can come together easily.
The Damper Control Module is approved for indoor use only and

should never be installed with any of its components exposed to
the elements. The Damper Control Module (and zone dampers)

may be installed in any area where the temperature remains

between --4

_

F to 158

_

F (--20

_

C to 70

_

C), and there is no

condensation. The cover must be installed to prevent damage from

other sources. Do not locate where it will be accessible to children.

It may be mounted in either vertical or horizontal position.
Remember that wiring access is likely the most important

consideration.

ELECTRICAL OPERATION HAZARD

Failure to follow this caution may result in equipment damage

or improper operation.
To prevent possible damage to the Damper Control Module,

DO NOT mount on plenum, ductwork, or flush against

furnace or fan coil.

CAUTION

!

Mounting Evolution Zone Control

There are two options for mounting the Evolution Zone Control to

the wall. First, become familiar with all plastic assembly pieces

shown in Fig. 3 through 10. The User Interface will snap together
with either the Recess Mount or the Surface Mount backplate.

Recess Mount

This provides the thinnest mounting configuration (See Fig. 4).

The backplate containing the recessed terminal block can be
mounted directly to the wall by cutting a hole 1 1/2” (38.1 mm)

wide by 2 1/8” (54 mm) high. Mark location and cut hole in wall.

NOTE

: Always ensure the Evolution Zone Control location is

acceptable before cutting any holes in wall.

Surface Mount

This provides surface mounting configuration, which allows use of

a small hole in the wall. A surface mount backplate is supplied (See

Fig. 5). Attach backplate as shown in Fig. 8, and the assembly will
mount directly to the wall requiring only a small hole in the wall

allowing a four wire connection to pass through.

NOTE

: Once Evolution Zone Control is secured to wall with the

backplate assembly (snapped together), care must be taken not to
bend or break the interlocking tabs when removing. Gently remove
Evolution Zone Control by rocking up/down until interlocking
tabs release.

Decorative Backplate

Supplied is a thin decorative backplate (see Fig. 6) to hide any

marks/screw holes left from the previous thermostat. This

decorative backplate (or beauty ring) can be used in either the
recess or surface mount installation by snapping it onto back of

recessed mount backplate or surface mount backplate before
securing to wall. See Fig. 9 and 10 for a larger decorative backplate

P/N SYSTXXOLBP01 (5.75” / 146 mm wide x 6” / 152 mm

high), which can be ordered separately.

A03185

Fig. 3 -- Evolution

t

Zone Control

BBU

IZ

01

--

B

Summary of Contents for EVOLUTION Zone Control SYSTXBBUIZ01-B

Page 1: ...all local electrical codes during installation All wiring must conform to local and national electrical codes Improper wiring or installation may damage the Evolution Zone System Recognize safety info...

Page 2: ...indoor unit outdoor unit and accessories accord ing to their instructions S Wire complete system according to this instruction S Setup commission and operate system according to this instruction to as...

Page 3: ...the elements The Damper Control Module and zone dampers may be installed in any area where the temperature remains between 4_F to 158_F 20_C to 70_C and there is no condensation The cover must be inst...

Page 4: ...essed Mount Interlocking Tabs 4 Recessed terminal block in wall 11 2 38 1 mm wide by 21 8 54 mm high A07150 Fig 7 Recessed Mount Assembly Surface Mount Backplate to wall Interlocking Tabs 4 A03191 Fig...

Page 5: ...CAL OPERATION HAZARD Failure to follow this caution may result in equipment damage or improper operation Improper wiring of the ABCD connector will cause the Evolution Zone System to operate improperl...

Page 6: ...olation relay coil to furnace or fan coil HUM and COM terminals will allow the Evolution Zone Control to automatically energize the HUM output during a call for humidification The N O relay contacts w...

Page 7: ...AC and the electric heater is not self identifying ELECTRIC HEATER NOT IDENTIFIED will appear See Fig 18 Press either Time or Temp buttons to select appropriate size of electric heater installed then...

Page 8: ...Press right side button to start Duct Assessment Duct Assessment will measure the relative size of the ductwork up to and through the dampers These measurements are used to control the correct amount...

Page 9: ...one schedule to other zones us ing NO or YES 11 Exit the scheduling mode by either closing the door or pressing the SCHEDULE button 12 If changes are made you will be asked to SAVE CHANGES YES NO INST...

Page 10: ...ll settings in Install Service menus to factory default settings Last 10 System Events S Yes No to reset last 10 system events under Service Info menu Setup Furnace Upon a first time start up of the E...

Page 11: ...midify mode is increased to reduce duct and register sweating Also increases minimum airflow during normal cooling opera tion to reduce duct sweating Heater Size S choices dependent upon fan coil mode...

Page 12: ...er run time Airflow Limits Since bypass damper is prohibited in this system this setting is used to select the maximum allowable noise airflow relationship into each zone based on air noise and comfor...

Page 13: ...e if the AC heat pump is a 2 stage model runs low speed only CHECKOUT MENUS CHECKOUT FURNACE HEAT PUMP HEATING HEAT PUMP COOLING HUMIDIFIER VENTILATOR BACK SELECT A03204 Fig 33 Checkout Menu The Check...

Page 14: ...MEDIUM S HIGH default S MAXIMUM Because there is no bypass damper the Zone Airflow Limit check will allow the installer to assess the airflow noise generated by the system providing the maximum amoun...

Page 15: ...er Control Module sensor will read leaving air temperature of the indoor unit The temperature information is for display purposes only The system does not react to this temperature reading Outdoor Coi...

Page 16: ...is adjustable from 4 to 6 cycles per hour This timer is defeated for one cycle when the desired temperature is manually changed It can also be defeated for one cycle by simultaneously pressing the Fan...

Page 17: ...a Equipment stage down or shut off if necessary b Fault history will record an event of AIRFLOW LIM ITED STAGEDOWN OCCURRED on stagedown and EXCESS STATIC PRESSURE if shut down c If shut down occurs o...

Page 18: ...e a mistake on the start up screens and hit the right side button to get to the run mode How do I get back to start up 1 Press the ADVANCED button for at least 10 seconds 2 Install Service menu will a...

Page 19: ...r Fault cooling mode only ventilator humidifier dehumidifier outdoor unit will be turned off Code 45 Control Circuitry Lockout NOTE For codes 13 14 and 21 the system will use heat pump heating exclusi...

Page 20: ...nge at any time specifications or designs without notice and without incurring obligations E2007 Bryant Heating Cooling Systems 7310 W Morris St Indianapolis IN 46231 Printed in China Edition Date 03...

Reviews: