background image

10

This menu has several layers, allowing modification of equipment
settings. No settings will need to be made at equipment (i.e. DIP

switches on a furnace). All configuration settings made effective
from this menu will override equipment configuration made by dip

switches. Fig. 27 shows all the information that can be found in the

SETUP

menu.

Setup -- Thermostat

Auto Mode Setup:

S

Enable/Disable Auto Changeover mode (default=En-
able).

S

Auto Changeover Time may be adjusted 5 to 120 min-
utes, (default = 30 minutes).

When Auto mode is enabled (factory default) a change from heat

to cool (or vice versa) will not occur until an opposite mode

demand has existed for 30 minutes. If the setpoint is changed, the
30 minute timer is deleted.

Heat/Cool Deadband:

S

0 to 6

_

F / 0 to 3.3

_

C, (default = 2

_

F / 1.1

_

F).

The minimum difference enforced between heating and cooling
desired temperatures. This can allow one setting to “push” the

other to maintain this difference.

Offsets:

This option allows calibration (or deliberate miscalibration) of the
temperature and humidity sensors. These offsets are added to the

actual temperature/humidity values (defaults=0).

S

Zone 1 Offset: --5 to +5

_

F (--2.8

_

C to +2.8

_

C).

S

Outside Temp Offset: --5 to +5

_

F (--2.8

_

C to +2.8

_

C).

S

Humidity Offset: --10 to +10%.

Cycles Per Hour:

S

Maximum cycles per hour = 4 (default) or 6.

S

Anticipator = 1 to 9 (default=3). This adjusts sensitivity

to temperature changes. 1 = most sensitive, 9 = least sen-
sitive.

S

If space is over--conditioning, increase the anticipator
setting.

S

If space is under--conditioning, decrease the anticipator

setting.

Programming:

S

ON (default)-- allows program schedule to be set by user.

S

OFF -- system becomes non--programmable

S

Periods Per Day = 2 or 4 (default=4)

S

Programmable Fan On/Off (default=Off). If ON is se-
lected, fan can be set to Auto, Low, Med, or High.

Smart Recovery:

S

On or Off (default=On)

Applies to programmable operation only. Will start recovery 90

minutes prior to schedule change in both heating and cooling

mode. Refer to operational information for more detail.

English/Metric Display:

S

_

F or

_

C (default =

_

F)

Reset Factory Defaults:
Program Schedule:

S

Yes/No to reset back to Energy Star default Time and
Temp schedules.

User Settings:

S

Yes/No to reset the user settings in the Advanced Setup
to factory default settings.

Install Settings:

S

Yes/No to reset install settings in Install/Service menus to
factory default settings.

Last 10 System Events:

S

Yes/No to reset last 10 system events under Service Info
menu.

Setup -- Furnace

Upon a first time start--up of the Evolution Zone Control, the

furnace DIP switch settings will be copied to the furnace setup
menu. Any changes can then be made from the Evolution Zone

Control.

Airflow:

S

COMFORT (default)

S

EFFICIENCY

Selects the airflow of the furnace when heating.

EFFICIENCY

is

the airflow used to meet specified ratings,

COMFORT

is a

decreased airflow used to increase the output air temperature and
provide increased comfort.

AC Airflow:

S

COMFORT (default) -- cooling airflow is varied depend-

ing on humidity and temperature demands settings. This
selection enables the full dehumidify and comfort capa-

bilities of the system. When COMFORT is not selected,
the unit will not run reduced aiflows for dehumidifica-
tion.

S

EFFICIENCY -- fixed airflow used to achieve specified
ratings -- no dehumidification airflow reduction. This is

nominally 350 CFM/ton, but will vary if a 2--stage out-
door unit is used.

S

MAXIMUM -- 400 CFM/ton.

Dehum Airflow:

S

NORMAL (factory default) -- When equipment is run-

ning to dehumidify, the airflow is allowed to adjust to a
minimum to satisfy the dehumidification call.

S

HIGH -- Minimum airflow during the dehumidify mode

is increased to reduce duct and register sweating. Also
increases minimum airflow during normal cooling opera-

tion to reduce duct sweating.

Low Heat Rise

S

ON

S

OFF (default)

Set to

ON

if the system contains a bypass humidifier. The

ON

setting will increase the furnace low heat airflow.

Staging

S

SYSTEM (default)

S

LOW

S

HIGH

Controls the staging of the furnace.

SYSTEM

setting will allow

the Evolution Zone Control to determine furnace staging.

LOW

will only run the low stage of furnace heat.

HIGH

will only run

the high stage of furnace heat.

G Terminal

This setup option selects desired operation when the R--G circuit
changes state on the furnace control board depending on setup.

S

DISABLED (Default)

S

FAN -- turns on fan to selected fan speed when G termi-

nal is energized. See Fig. 28.

S

FAN SPEED -- select Low, Med, High for all zones
when G terminal is energized

S

SHUTDOWN -- shuts off fan and equipment when initi-
ated. This function may be activated by a dry contact

from an external device such as a float switch or a relay.
User selects whether the contact is NC -- normally closed

(default) or NO -- normally open. User Interface displays
SYSTEM MALFUNCTION on screen and registers G

BBU

IZ

01

--

B

Summary of Contents for EVOLUTION Zone Control SYSTXBBUIZ01-B

Page 1: ...all local electrical codes during installation All wiring must conform to local and national electrical codes Improper wiring or installation may damage the Evolution Zone System Recognize safety info...

Page 2: ...indoor unit outdoor unit and accessories accord ing to their instructions S Wire complete system according to this instruction S Setup commission and operate system according to this instruction to as...

Page 3: ...the elements The Damper Control Module and zone dampers may be installed in any area where the temperature remains between 4_F to 158_F 20_C to 70_C and there is no condensation The cover must be inst...

Page 4: ...essed Mount Interlocking Tabs 4 Recessed terminal block in wall 11 2 38 1 mm wide by 21 8 54 mm high A07150 Fig 7 Recessed Mount Assembly Surface Mount Backplate to wall Interlocking Tabs 4 A03191 Fig...

Page 5: ...CAL OPERATION HAZARD Failure to follow this caution may result in equipment damage or improper operation Improper wiring of the ABCD connector will cause the Evolution Zone System to operate improperl...

Page 6: ...olation relay coil to furnace or fan coil HUM and COM terminals will allow the Evolution Zone Control to automatically energize the HUM output during a call for humidification The N O relay contacts w...

Page 7: ...AC and the electric heater is not self identifying ELECTRIC HEATER NOT IDENTIFIED will appear See Fig 18 Press either Time or Temp buttons to select appropriate size of electric heater installed then...

Page 8: ...Press right side button to start Duct Assessment Duct Assessment will measure the relative size of the ductwork up to and through the dampers These measurements are used to control the correct amount...

Page 9: ...one schedule to other zones us ing NO or YES 11 Exit the scheduling mode by either closing the door or pressing the SCHEDULE button 12 If changes are made you will be asked to SAVE CHANGES YES NO INST...

Page 10: ...ll settings in Install Service menus to factory default settings Last 10 System Events S Yes No to reset last 10 system events under Service Info menu Setup Furnace Upon a first time start up of the E...

Page 11: ...midify mode is increased to reduce duct and register sweating Also increases minimum airflow during normal cooling opera tion to reduce duct sweating Heater Size S choices dependent upon fan coil mode...

Page 12: ...er run time Airflow Limits Since bypass damper is prohibited in this system this setting is used to select the maximum allowable noise airflow relationship into each zone based on air noise and comfor...

Page 13: ...e if the AC heat pump is a 2 stage model runs low speed only CHECKOUT MENUS CHECKOUT FURNACE HEAT PUMP HEATING HEAT PUMP COOLING HUMIDIFIER VENTILATOR BACK SELECT A03204 Fig 33 Checkout Menu The Check...

Page 14: ...MEDIUM S HIGH default S MAXIMUM Because there is no bypass damper the Zone Airflow Limit check will allow the installer to assess the airflow noise generated by the system providing the maximum amoun...

Page 15: ...er Control Module sensor will read leaving air temperature of the indoor unit The temperature information is for display purposes only The system does not react to this temperature reading Outdoor Coi...

Page 16: ...is adjustable from 4 to 6 cycles per hour This timer is defeated for one cycle when the desired temperature is manually changed It can also be defeated for one cycle by simultaneously pressing the Fan...

Page 17: ...a Equipment stage down or shut off if necessary b Fault history will record an event of AIRFLOW LIM ITED STAGEDOWN OCCURRED on stagedown and EXCESS STATIC PRESSURE if shut down c If shut down occurs o...

Page 18: ...e a mistake on the start up screens and hit the right side button to get to the run mode How do I get back to start up 1 Press the ADVANCED button for at least 10 seconds 2 Install Service menu will a...

Page 19: ...r Fault cooling mode only ventilator humidifier dehumidifier outdoor unit will be turned off Code 45 Control Circuitry Lockout NOTE For codes 13 14 and 21 the system will use heat pump heating exclusi...

Page 20: ...nge at any time specifications or designs without notice and without incurring obligations E2007 Bryant Heating Cooling Systems 7310 W Morris St Indianapolis IN 46231 Printed in China Edition Date 03...

Reviews: