background image

38

PRE-START-UP

Proceed as follows to inspect and prepare the unit for initial
start-up:

1. Remove all access panels.

2. Read and follow instructions on all WARNING, CAU-

TION, and INFORMATION labels attached to or
shipped with unit.

3. Make the following inspections:

a. Inspect for shipping and handling damages such

as broken lines, loose parts, or disconnected
wires.

b. Inspect for oil at all refrigerant tubing connec-

tions and on unit base. Detecting oil generally
indicates a refrigerant leak. Leak-test all refrig-
erant tubing connections using electronic leak
detector, halide torch, or liquid-soap solution.

c. Inspect all field-wiring and factory-wiring con-

nections. Be sure that connections are completed
and tight.

d. Inspect coil fins. If damaged during shipping and

handling, carefully straighten fins with a fin
comb.

4. Verify the following:

a. Make sure that condenser-fan blades are

correctly positioned in fan orifice. Refer to
Condenser-Fan Adjustment section on page 42
for more details.

b. Make sure that air filters are in place.

c. Make sure that condensate drain trap is filled

with water to ensure proper drainage.

d. Make sure that all tools and miscellaneous loose

parts have been removed.

e. Make sure that the start-up checklist has been

performed and filled out.

NOTE: 

Ensure wiring does not contact any refrigerant

tubing.

START-UP

I. UNIT PREPARATION

Make sure that unit has been installed in accordance with
these installation instructions and applicable codes.

II. RETURN-AIR FILTERS

Make sure correct filters are installed in unit (see Table 1).
Do not operate unit without return-air filters.

III. OUTDOOR-AIR INLET SCREENS

Outdoor-air inlet screens must be in place before operating
unit.

IV. COMPRESSOR MOUNTING

Compressors are internally spring mounted. Do not loosen or
remove compressor holddown bolts.

V. INTERNAL WIRING

Check all electrical connections in unit control boxes; tighten
as required.

VI. REFRIGERANT SERVICE PORTS

Each refrigerant system has 4 Schrader-type service gage
ports: one on the suction line, one on the liquid line, and 2 on
the compressor discharge line. Be sure that caps on the ports
are tight.

VII. HIGH FLOW VALVES

Two high flow refrigerant valves are located on the compres-
sor hot gas and suction tubes. Large black plastic caps dis-
tinguish these valves with o-rings located inside the caps.
These valves can not be accessed for service in the field.
Ensure the plastic caps are in place and tight or the possibil-
ity of refrigerant leakage could occur.

VIII. COMPRESSOR ROTATION

On 3-phase units, it is important to be certain the scroll
compressor is rotating in the proper direction. To determine
whether or not compressor is rotating in the proper direction:

1. Connect service gages to suction and discharge pres-

sure fittings.

2. Energize the compressor.

3. The suction pressure should drop and the discharge

pressure should rise, as is normal on any start-up.

If the suction pressure does not drop and the discharge pres-
sure does not rise to normal levels:

1. Note that the evaporator fan is probably also rotating

in the wrong direction.

2. Turn off power to the unit and install lockout tag.

3. Reverse any two of the unit power leads.

4. Turn on power to the unit.

The suction and discharge pressure levels should now move
to their normal start-up levels.

NOTE: 

When the compressor is rotating in the wrong direc-

tion, the unit makes an elevated level of noise and does not
provide heating or cooling.

WARNING: 

 Failure to observe the following warn-

ings could result in serious personal injury:

1. Follow recognized safety practices and wear

protective goggles when checking or servicing
refrigerant system.

2. Do not operate compressor or provide any elec-

tric power to unit unless compressor terminal
cover is in place and secured.

3. Do not remove compressor terminal cover until

all electrical sources are disconnected and prop-
erly tagged.

4. Relieve all pressure from system before touch-

ing or disturbing anything inside terminal box
if refrigerant leak is suspected around compres-
sor terminals. Use accepted methods to recover
refrigerant.

5. Never attempt to repair soldered connection

while refrigerant system is under pressure.

6. Do not use torch to remove any component. Sys-

tem contains oil and refrigerant under pres-
sure. To remove a component, wear protective
goggles and proceed as follows:

a. Shut off electrical power to unit and install

lockout tag.

b. Relieve all pressure from system using

both high and low-pressure ports. Use
accepted methods to recover refrigerant.

c. Cut component connection tubing with tub-

ing cutter and remove component from
unit.

d. Carefully unsweat remaining tubing stubs

when necessary. Oil can ignite when
exposed to torch flame.

CAUTION: 

 Compressor damage will occur if rota-

tion is not immediately corrected.

Summary of Contents for DURAPAC PLUS 551B

Page 1: ...gasket supplied with the roof curb as shown in Fig 2 Improperly applied gasket can also result in air leaks and poor unit performance Curb should be level This is necessary for unit drain to func tion...

Page 2: ...G AND PLACE UNIT Inspect unit for transportation damage File any claim with transportation agency Keep unit upright and do not drop Spreader bars are not required if top crating is left on unit Roller...

Page 3: ...RBTMPWR001A01 and 2A01 are for thru the curb gas type Packages CRBTMPWR003A01 and 4A01 are for thru the bottom type gas connections ROOF CURB ACCESSORY A UNIT SIZE CRRFCURB003A01 1 2 356 551B090 150 C...

Page 4: ...rating weights with the Perfect Humidity dehumidification system CAUTION All panels must be in place when rigging Fig 6 Rigging Details 551B OPERATING WEIGHT A B C lb kg in mm in mm in mm 090 755 343...

Page 5: ...5 Fig 7 Base Unit Dimensions...

Page 6: ...5 Nominal Cfm Standard 3000 3400 4000 5000 Maximum Continuous Bhp Standard 2 90 2 90 3 70 5 25 High Static 4 20 4 20 5 25 Motor Frame 56 56 56 56 Fan Rpm Range Standard 840 1085 840 1085 860 1080 830...

Page 7: ...must be within range indicated on unit nameplate see Table 2 On 3 phase units voltages between phases must be balanced within 2 and the current within 10 Use the formula shown in Table 2 Note 2 on pag...

Page 8: ...80 66 136 575 3 60 STD NO 518 632 4 8 34 0 4 8 34 0 2 0 7 3 4 14 6 20 15 94 17 0 16 4 23 8 20 22 95 34 0 32 7 44 3 45 41 95 STD YES 518 632 4 8 34 0 4 8 34 0 2 0 7 3 4 16 8 20 17 96 17 0 16 4 26 5 20...

Page 9: ...68 7 70 63 171 50 0 60 1 66 1 80 75 171 STD YES 414 508 8 3 62 5 8 3 62 5 2 0 7 4 8 27 6 20 29 172 13 9 16 7 30 3 35 29 173 16 5 19 8 33 5 35 31 173 33 0 39 7 58 3 60 54 173 41 7 50 2 71 4 80 66 173 5...

Page 10: ...n voltage of 215 v kW new 16 kW 215 240 2 kW new 12 8 kW rating at 215 v FLA Full Load Amps HACR Heating Air Conditioning and Refrigeration IFM Indoor Evaporator Fan Motor LRA Locked Rotor Amps MCA Mi...

Page 11: ...lling holes in basepan C Heat Anticipator Settings For units with electric heat set heat anticipator settings as shown in Table 4 VI STEP 6 ADJUST FACTORY INSTALLED OPTIONS A Disconnect Switch The opt...

Page 12: ...ions included with the Bryant Light Commercial Thermi distat device for more information Fig 12 Light Commercial Thermidistat Device Fig 13 Typical Perfect Humidity Dehumidification System Humidistat...

Page 13: ...gn screw holes on hood with screw holes on side of manual outdoor air damper See Fig 16 and 17 Secure hood with 8 screws from Step 6 8 Adjust minimum position setting of the damper blade by adjusting...

Page 14: ...ivider Push the filter into position past the open filter clips Close the filter clips to lock the filter into place See Fig 24 8 Caulk the ends of the joint between the unit top panel and the hood to...

Page 15: ...oor Air Temperature POT Potentiometer RAT Return Air Temperature Potentiometer Defaults Settings Power Exhaust Middle Minimum Pos Fully Closed DCV Max Middle DCV Set Middle Enthalpy C Setting NOTES 1...

Page 16: ...2 is an accessory aspirator box required for duct mounted applications CRCBDIOX005A00 is an accessory that contains both 33ZCSENCO2 and 33ZCASPCO2 accessories TEMPERATURE F RESISTANCE ohms 58 200 250...

Page 17: ...ing location See Fig 19 When the outdoor air enthalpy rises above the outdoor enthalpy changeover set point the outdoor air damper moves to its minimum position The outdoor enthalpy changeover set poi...

Page 18: ...1 2 1 4 1 6 1 8 2 0 2 2 2 4 2 6 2 8 3 0 3 2 3 4 3 6 3 8 4 0 4 2 4 4 4 6 9 0 1 0 0 8 0 7 0 6 0 5 0 4 0 3 0 20 10 E N T H A L P Y B T U P E R P O U N D D R Y A I R 85 29 90 32 95 35 100 38 105 41 110 4...

Page 19: ...er position remotely remove the factory installed jumper on the P and P1 terminals on the EconoMi er IV controller Wire the field supplied poten tiometer to the P and P1 terminals on the EconoMi er IV...

Page 20: ...ection 5 Press Mode to exit and resume normal operation The custom settings of the CO2 sensor can be changed any time after the sensor is energized Follow the steps below to change the non standard se...

Page 21: ...rest keyway of pulley hub and tighten setscrew See Table 1 for speed change for each full turn of pulley flange To align fan and motor pulleys 1 Loosen fan pulley setscrews 2 Slide fan pulley along fa...

Page 22: ...EN 0 1 2 1 11 2 2 21 2 3 31 2 4 41 2 5 51 2 6 090 102 1085 1060 1035 1010 985 960 935 910 890 865 840 120 1080 1060 1035 1015 990 970 950 925 905 880 860 150 1130 1112 1087 1062 1037 1212 987 962 937...

Page 23: ...he motor can be utilized with confidence Using fan motors up to the ratings shown will not result in nuisance trip ping or premature motor failure Unit warranty will not be affected For additional inf...

Page 24: ...15 2004 3100 646 1 15 1071 711 1 41 1313 770 1 68 1568 824 1 97 1835 875 2 27 2114 3200 663 1 25 1162 726 1 51 1411 784 1 79 1672 837 2 09 1944 888 2 39 2229 3300 679 1 35 1259 741 1 62 1514 798 1 91...

Page 25: ...1 86 1737 827 2 16 2017 878 2 48 2308 926 2 80 2610 3600 729 1 70 1583 787 1 99 1857 841 2 30 2144 892 2 62 2441 939 2 95 2749 3700 746 1 83 1703 803 2 13 1985 856 2 44 2277 906 2 77 2580 953 3 10 28...

Page 26: ...000 697 1 37 1281 753 1 58 1474 804 1 79 1666 852 1 99 1857 897 2 20 2048 4100 712 1 47 1370 766 1 68 1567 817 1 89 1764 864 2 10 1960 909 2 31 2155 4200 726 1 57 1462 780 1 79 1665 830 2 00 1866 876...

Page 27: ...67 817 1 89 1764 864 2 10 1960 909 2 31 2155 4200 726 1 57 1462 780 1 79 1665 830 2 00 1866 876 2 22 2067 920 2 43 2268 4300 741 1 67 1559 794 1 89 1767 843 2 12 1973 889 2 34 2179 932 2 56 2384 AIRFL...

Page 28: ...99 882 2 49 2320 926 2 72 2541 968 2 96 2760 4700 800 2 14 1991 849 2 38 2219 895 2 62 2445 939 2 86 2670 980 3 10 2895 4800 815 2 26 2111 863 2 51 2344 909 2 76 2575 952 3 01 2805 993 3 25 3034 4900...

Page 29: ...2 76 2575 952 3 01 2805 993 3 25 3034 4900 829 2 40 2235 877 2 65 2473 922 2 91 2709 965 3 16 2944 1005 3 41 3178 5000 844 2 54 2365 891 2 80 2608 936 3 06 2849 978 3 31 3089 1018 3 57 3328 AIRFLOW C...

Page 30: ...53 977 3 78 3525 1018 4 07 3796 1057 4 36 4066 1094 4 65 4335 5700 950 3 67 3421 992 3 97 3698 1032 4 26 3974 1070 4 56 4249 1107 4 85 4522 5800 965 3 85 3594 1006 4 16 3876 1046 4 46 4157 1084 4 76 4...

Page 31: ...8 660 1 23 1151 727 1 53 1422 787 1 82 1702 841 2 13 1991 3300 596 1 03 957 672 1 32 1228 738 1 61 1506 797 1 92 1792 851 2 24 2088 3400 609 1 10 1030 684 1 40 1308 749 1 71 1593 808 2 02 1887 861 2 3...

Page 32: ...2 2 46 2294 3600 635 1 27 1187 708 1 59 1481 771 1 91 1781 829 2 24 2088 882 2 58 2403 3700 649 1 36 1272 720 1 69 1573 783 2 02 1881 840 2 35 2195 892 2 70 2517 3750 655 1 41 1316 726 1 74 1621 789 2...

Page 33: ...09 1 42 1322 761 1 61 1506 812 1 82 1695 860 2 03 1890 4100 668 1 31 1223 722 1 51 1405 773 1 71 1593 822 1 92 1786 870 2 13 1984 4200 682 1 40 1305 734 1 60 1492 784 1 80 1683 833 2 02 1880 880 2 23...

Page 34: ...773 1 71 1593 822 1 92 1786 870 2 13 1984 4200 682 1 40 1305 734 1 60 1492 784 1 80 1683 833 2 02 1880 880 2 23 2082 4300 696 1 49 1392 747 1 70 1582 796 1 91 1777 844 2 12 1979 890 2 34 2184 AIRFLOW...

Page 35: ...751 1 91 1778 798 2 13 1984 844 2 35 2195 889 2 59 2412 932 2 82 2633 4800 765 2 02 1885 812 2 25 2095 856 2 48 2310 900 2 71 2531 942 2 95 2756 4900 779 2 14 1996 825 2 37 2210 869 2 61 2430 912 2 8...

Page 36: ...856 2 48 2310 900 2 71 2531 942 2 95 2756 4900 779 2 14 1996 825 2 37 2210 869 2 61 2430 912 2 85 2654 953 3 09 2883 5000 793 2 26 2112 838 2 50 2330 881 2 74 2554 923 2 98 2782 965 3 23 3014 AIRFLOW...

Page 37: ...3 99 3716 1021 4 26 3976 1057 4 55 4240 5900 921 3 61 3370 959 3 89 3626 997 4 17 3885 1033 4 45 4149 1069 4 74 4416 6000 935 3 79 3536 973 4 07 3795 1010 4 35 4059 1046 4 64 4326 1082 4 93 4598 6100...

Page 38: ...s with o rings located inside the caps These valves can not be accessed for service in the field Ensure the plastic caps are in place and tight or the possibil ity of refrigerant leakage could occur V...

Page 39: ...er IV When free cooling is not available the compressors will be controlled by the zone thermostat When free cooling is avail able the outdoor air damper is modulated by the EconoMi er IV control to p...

Page 40: ...coil When in subcooling mode there is a slight decrease in sys tem total gross capacity 5 less a lower gross sensible capacity 20 less and a greatly increased latent capacity up to 40 more Hot Gas Reh...

Page 41: ...pletion 6 Reinstall economizer or two position damper and filters 7 Reconnect wiring 8 Replace access panels B Condenser Coils Inspect coils monthly Clean condenser coils annually and as required by l...

Page 42: ...he suction line Mount the temperature sensing device on the suction line and insulate it so that outdoor ambient temperature does not affect the reading Indoor air cfm must be within the normal operat...

Page 43: ...43 Fig 47 Cooling Charging Charts Standard 551B090 Unit Fig 48 Cooling Charging Charts Standard 551B102 Unit...

Page 44: ...44 Fig 49 Cooling Charging Charts Standard 551B120 Unit Fig 50 Cooling Charging Charts Standard 551B150 Unit...

Page 45: ...ification coil liquid line solenoid valve MUST be energized to use the charging charts and the outdoor motor speed controller jumpered to run the fan at full speed Fig 52 Cooling Charging Chart 581B10...

Page 46: ...Replace Restriction in refrigerant system Locate restriction and remove Compressor s Operates Continuously Dirty air filter Replace filter Unit undersized for load Decrease load or increase unit size...

Page 47: ...ification Coil Energized Thermostatic expansion valve TXV 1 Check TXV bulb mounting and secure tightly to suction line 2 Replace TXV if stuck open or closed PROBLEM CAUSE REMEDY Reheat Mode Will Not E...

Page 48: ...tings and wiring to normal after completing troubleshooting D DCV Demand Controlled Ventilation and Power Exhaust To check DCV and Power Exhaust 1 Make sure EconoMi er IV preparation procedure has bee...

Page 49: ...py to the ABCD set point Power at N terminal determines Occupied Unoccupied setting 24 vac Occupied no power Unoccupied Modulation is based on the supply air sensor signal Modulation is based on the D...

Page 50: ...Heat anticipator settings 11 High flow valves 38 High pressure switch 6 Horizontal units 1 2 Humidistat 12 Indoor air quality sensor 18 Low pressure switch 6 Manual outdoor air damper 13 Mounting Unit...

Page 51: ......

Page 52: ...N AND IN PLACE VERIFY THAT UNIT INSTALLATION IS LEVEL CHECK FAN WHEEL AND PROPELLER FOR LOCATION IN HOUSING AND ORIFICE AND CHECK THAT SETSCREW IS TIGHT CHECK PULLEY ALIGNMENT AND BELT TENSION PER INS...

Reviews: