Table 18 — Fan Performance — 580F240360 (High Heat Units)*
LEGEND
*Standard low-medium static drive range is 1002 to 1151 rpm. Alternate
high-static drive range is 1193 to 1369. Other rpms require a field-
supplied drive.
Refer to page 32 for general Fan Performance Data notes.
NOTE:
Maximum continuous bhp for the standard motor is 8.7 (for 208/
230-v units) and 9.5 (for 460-v units). The maximum continuous watts is
7915 (for 208/230-v units) and 8640 (for 460-v units). Do not adjust
motor rpm such that motor maximum bhp and/or watts is exceeded at
the maximum operating cfm. See Table 24 for more information.
AIRFLOW
(Cfm)
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
0.2
0.4
0.6
0.8
1.0
Rpm
Watts
Bhp
Rpm
Watts
Bhp
Rpm
Watts
Bhp
Rpm
Watts
Bhp
Rpm
Watts
Bhp
6,000
868
2752
3.26
934
2987
3.54
997
3227
3.83
1058
3470
4.12
1115
3716
4.41
6,500
929
3201
3.80
991
3436
4.08
1051
3675
4.36
1108
3917
4.65
1162
4163
4.94
7,000
991
3687
4.37
1049
3923
4.65
1105
4161
4.94
1159
4403
5.22
1211
4647
5.51
7,500
1054
4211
5.00
1109
4447
5.28
1161
4686
5.56
1213
4926
5.84
1262
5170
6.13
8,000
1117
4773
5.66
1168
5009
5.94
1218
5247
6.22
1267
5488
6.51
1314
5731
6.80
8,500
1180
5373
6.37
1229
5609
6.65
1277
5847
6.94
1323
6088
7.22
1368
6331
7.51
9,000
1244
6011
7.13
1290
6247
7.41
1335
6485
7.69
1380
6726
7.98
1423
6968
8.27
9,500
1308
6687
7.93
1352
6924
8.21
1395
7162
8.50
1437
7402
8.78
1479
7644
9.07
10,000
1372
7401
8.78
1414
7638
9.06
1455
7876
9.34
1496
8117
9.63
1535
8358
9.92
AIRFLOW
(Cfm)
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
1.2
1.4
1.6
1.8
2.0
Rpm
Watts
Bhp
Rpm
Watts
Bhp
Rpm
Watts
Bhp
Rpm
Watts
Bhp
Rpm
Watts
Bhp
6,000
1171
3965
4.70
1224
4216
5.00
1276
4469
5.30
1326
4726
5.61
1374
4983
5.91
6,500
1215
4410
5.23
1266
4659
5.53
1316
4911
5.83
1364
5165
6.13
1411
5421
6.43
7,000
1262
4894
5.81
1311
5142
6.10
1358
5392
6.40
1404
5645
6.70
1449
5899
7.00
7,500
1310
5415
6.42
1357
5663
6.72
1403
5912
7.01
1447
6164
7.31
1490
6416
7.61
8,000
1360
5976
7.09
1405
6222
7.38
1449
6471
7.68
1492
6721
7.97
1533
6973
8.27
8,500
1412
6575
7.80
1455
6821
8.09
1497
7068
8.39
1538
7318
8.68
—
—
—
9,000
1465
7212
8.56
1506
7457
8.85
1547
7705
9.14
—
—
—
—
—
—
9,500
1519
7888
9.36
—
—
—
—
—
—
—
—
—
—
—
—
10,000
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
AIRFLOW
(Cfm)
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
2.2
2.4
2.6
2.8
3.0
Rpm
Watts
Bhp
Rpm
Watts
Bhp
Rpm
Watts
Bhp
Rpm
Watts
Bhp
Rpm
Watts
Bhp
6,000
1422
5243
6.22
1468
5505
6.53
1513
5768
6.84
—
—
—
—
—
—
6,500
1456
5679
6.74
1501
5938
7.04
1544
6199
7.35
—
—
—
—
—
—
7,000
1493
6155
7.30
1536
6412
7.61
—
—
—
—
—
—
—
—
—
7,500
1533
6670
7.91
—
—
—
—
—
—
—
—
—
—
—
—
8,000
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
8,500
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
9,000
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
9,500
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
10,000
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
Bhp
—
Brake Horsepower
Watts —
Input Watts to Motor
Summary of Contents for DuraPac 580F Series
Page 3: ... 3 Fig 1B Roof Curb Details 580F300 A A ...
Page 25: ... 25 Fig 36 Perfect Humidity Dehumidification Package Operation Diagram Single Circuit Shown ...
Page 40: ... 40 Fig 45 Typical Wiring Schematic 580F240 208 230 V Shown ...
Page 41: ... 41 Fig 46 Typical Component Arrangement 580F240 Shown ...
Page 50: ...Copyright 2006 Bryant Heating Cooling Systems Printed in U S A CATALOG NO 04 53580003 01 ...
Page 51: ......