OPERATIONAL INFORMATION

FIVE-MINUTE COMPRESSOR TIMEGUARD

This timer prevents the compressor from starting unless it has been off for at least 5 minutes. It can be defeated for 1 cycle by simultaneously
pressing the FAN mode button and the INCREASE TEMPERATURE button.

FIFTEEN-MINUTE CYCLE TIMER

This timer prevents the start of a heating or cooling cycle until at least 15 minutes after the last start of the same cycle. Its function is to assure
that equipment is not cycled more than 4 times per hour. This timer is defeated for 1 cycle when the desired temperature is manually changed.
It can also be defeated for 1 cycle by simultaneously pressing the FAN mode button and the INCREASE TEMPERATURE button.

FIFTEEN-MINUTE STAGING TIMER

In multistage heating or cooling, this timer prevents any higher stage from turning on until the preceeding stage has been on for 15 minutes. This
timer is defeated if the temperature error is greater than 5 degrees (usually due to a large change in desired temperature).

TWO-MINUTE MINIMUM ON TIME

In normal operation, when a stage turns on, it will not turn off for a minimum of 2 minutes.

HEAT/COOL SETPOINTS (DESIRED TEMPERATURES)

A minimum difference of 3 degrees is enforced between heating and cooling desired temperatures. This is done by allowing one setting to "push"
the other, to maintain this difference.

AUTO CHANGEOVER

When the auto changeover mode is selected, a change from heat to cool (or vice versa) will not occur until an opposite mode demand has existed
for 20 minutes. If the setpoint is changed, the 20 minute requirement is deleted.

POWER ON CHECK

When AC power is first applied, all segments of display are turned on for a few seconds. Following this, the temperature display reads dF for a
few seconds to indicate that it is a dual fuel thermostat.

ERROR CODES

E1 - If thermostat cannot properly read room temperature, the room temperature display will indicate E1 and thermostat will enter FREEZE

PROTECT mode. When outdoor temperature is below 50˚F furnace will operate for sufficient time every half hour to keep home from
freezing. The ON time is given by the formula: Minutes ON equals 15 minus (outdoor temperature in ˚F divided by 4).

E2 - If the AC line voltage drops below a minimum (brownout) level, all outputs are turned off and the display indicates E2. This condition will

remain for 15 seconds after proper line voltage is restored. If the AC line voltage disappears completely, the display will immediately go
blank.

E3 - If thermostat cannot properly read outdoor temperature E3 will be displayed in place of room temperature. The thermostat will continue to

operate, but will only use furnace in HEAT mode.

AUXILIARY HEAT ICON

This icon is displayed when the furnace is operating.

SMART RECOVERY

With Smart Recovery selected, the transition out of a heating setback begins a fixed time period before the selected recovery time and gradually
adjusts room temperature so that the desired temperature will be achieved at the selected recovery time. The fixed time period is 1 hr for furnaces
and 1.5 hrs for heat pumps.

THERMOSTAT TROUBLESHOOTING

SYMPTOM

WHAT TO CHECK

No LCD on temperature display

Check for 24 VAC between R and C at terminal connections. Both R and C must be connected for proper opera-
tion.

Trouble

on temperature display

Outdoor temperature sensor reading out of range. An attempt to read outdoor temperature results in

--

on dis-

play. Check for shorted, open, or failed outdoor temperature sensor.

E2

on temperature display

Brownout condition or too low of voltage to thermostat. Double check wiring and check for 24 VAC between R and
C. E2 will clear 15 seconds after proper voltage is restored.

E1

on temperature display

Temperature sensor reading out of range. Check sensor for damage. If recycling power does not clear display,
thermostat should be replaced.

Clean Filter

on temperature display

After the selected number of hours of blower operation

clean filter

will display on LCD. This is to remind the ho-

meowner to

check

filter. Press

reset filter

button to clear display and reset timer to 0.

Cooling will not come on

Select COOL mode. Decrease cooling setpoint to 10 degrees below room temperature. Simultaneously press FAN
and INCREASE TEMPERATURE buttons to defeat timers. Check for 24 VAC at Y/Y2 terminal. If present, thermo-
stat is OK and problem is with equipment or wiring. If not present, replace thermostat.

Heating will not come on

Select HEAT mode. Increase heating setpoint to 2 or 3 degrees (not more) above room temperature. Simulta-
neously press FAN and INCREASE TEMPERATURE buttons to defeat timers for 1 cycle. Check for 24 VAC at
Y/Y2 terminal (single-speed HP) or Y1/W2 terminal (2-speed HP) within 10 seconds. Increase heating setpoint to
7 or 8 degrees above room temperature. Check for 24VAC at W/W1 terminal (single-speed HP) or Y/Y2 terminal
(2-speed HP) within 2 minutes. After 2 minutes check for 24VAC at Y1/W2 terminal (single-speed HP) or W/W1
terminal (2-speed HP).

—7—

Summary of Contents for DUAL FUEL THERMOSTAT TSTAT

Page 1: ...irements Fore most is that furnace and HP must not be allowed to operate at same time except during HP defrost A second is to have furnace complete a heating cycle once it is turned on A third is the need to have HP not operate at all when outdoor temperatures are below a certain value Finally HP and furnace must work together properly to provide an efficient and comfortable defrost These requirem...

Page 2: ...P heating call to operate compressor at high speed and adjust blower for high speed HP operation HEATING OPERATION SINGLE STAGE FURNACE W W1 causes furnace to operate Furnace controls its own blower at heating speed HEATING OPERATION TWO STAGE FURNACE THERMOSTAT CONTROL Low fire W W1 causes furnace to operate at low fire Furnace controls its own blower at low heating speed High fire Y1 W2 is added...

Page 3: ...e will arrive at the programmed temperature at the programmed time TO SET OFF for smart recovery This is the factory default ON for normal recovery SWITCH C DISABLE LOW AMBIENT COOLING Use to allow or prevent cooling operation below an outdoor temperature of 55 F Prevention of cooling below 55 F adds to compressor reliability If outdoor temperature sensor fails or is disconnected cooling is allowe...

Page 4: ...lter 1200 to 1600 hours or electronic air cleaner 1600 to 2400 hours of blower operation TO SELECT 1 Enter configuration mode 2 Press RESET FILTER button to display OF off or digits 1 through 9 3 Use up and down buttons to move between selections Total hours equals 400 times the displayed number OF off turns feature off 4 During the selection process the CLEAN FILTER icon will remain on even if OF...

Page 5: ...m is entered VIII CHECKLIST 1 Put away tools and instruments and clean up debris 2 Review Homeowner s Guide with owner 3 Leave literature packet with owner Fig 2 Single Stage Furnace with Single Speed Heat Pump A95215 Y Y2 W W1 R 24 VAC HOT FAN FURNACE COMPRESSOR RVS COOLING N A DUAL FUEL THERMOSTAT SINGLE SPEED HEAT PUMP 24 VAC COM RVS HEATING RVS SENSING OUTDOOR SENSOR CONNECTION G R R W Y Y G C...

Page 6: ...1 W2 TWO STAGE OR VARIABLE SPEED FURNACE W2 O SEE NOTES 1 AND 2 W W1 Y Y2 O Y1 W2 Y1 W3 OUTDOOR TEMPERATURE SENSOR WIRING DIAGRAM NOTES 1 Underlined letter on dual terminal indicates its usage For Example O W2 means O O W2 means W2 Outdoor Temperature Sensor must be attached in all dual fuel installations Jumper wire between O W2 and L thermostat terminals MUST be present 2 Y1 and O connections to...

Page 7: ...ge is restored If the AC line voltage disappears completely the display will immediately go blank E3 If thermostat cannot properly read outdoor temperature E3 will be displayed in place of room temperature The thermostat will continue to operate but will only use furnace in HEAT mode AUXILIARY HEAT ICON This icon is displayed when the furnace is operating SMART RECOVERY With Smart Recovery selecte...

Page 8: ... 1995 BDP Co P O Box 70 Indianapolis IN 46206 Printed in U S A 8 tstat06 Catalog No 92 33TS TA28B ...

Reviews: