Furnace

Airflow

Airflow

Adapters

A05274

Fig. 5 -- Use of Furnace Adapters

       Note (optional): Slip return

duct adapters onto flanges

on air return duct side

A05277

Fig. 6 -- Use of Return Duct Adapters

Step 9

Wiring

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury

or death.
Before installing or servicing system, always turn off main

power to system. There may be more than 1 disconnect

switch.

!

WARNING

EQUIPMENT DAMAGE HAZARD

Failure to follow this caution may result in equipment

damage or improper operation.
This unit cannot be powered directly from blower motor

leads. Voltages can exceed 190 VAC (120v motors). Do

not wire directly to blower motor. Wiring to blower motor

will damage power supply and void warranty.

CAUTION

!

a. Ensure power has been removed from the heating and

cooling system.

b. Turn the Perfect Air

t

Purifier power switch off.

c. Connect the power cord to the power supply connector

(see Fig. 7).

d. Route the power cord through nearest cabinet hole and

protect with enclosed cable connector. Zip ties have

been enclosed to secure the power cord to the side of the

power supply.

e. Attach the quick connect terminals to the furnace

EAC--1 and EAC--2 spade connections. Attach the

ground ring to furnace chassis ground.

NOTE

: The Perfect Air

t

Purifier is to be powered by 115v/60

Hz.

NOTE

: The Perfect Air

t

Purifier should only be powered when

airflow is present. The furnace control EAC spade connections
provide power only when the furnace blower is operating. If EAC
connections are not available, an alternative airflow sensing
mechanism must be used to ensure the Perfect Air

t

Purifier is

only powered when airflow is present. Contact a local Bryant
distributor for information on approved alternatives.

UNIT COMPONENT DAMAGE HAZARD

Failure to follow this caution may result in equipment

damage or improper operation.
Black Lead -- Connect to HOT (L1) or EAC--1 when

provided.

White Lead -- Connect to Neutral (L2) or EAC--2 when

provided.

Green/Ground Lead -- Connect to Appliance Ground

(Chassis)

CAUTION

!

GAP

A

Summary of Contents for AIRT PURIFIER

Page 1: ...ptured particles are killed by electrical current flow and ion bombardment A06054 Fig 1 GAPA Unit SAFETY CONSIDERATIONS Improper installation adjustment alteration service maintenance or use can cause explosion fire electrical shock or other conditions which may cause personal injury or property damage Consult a qualified installer service agency or your distributor or branch for information or as...

Page 2: ... If the return air duct or furnace openings do not fit the Perfect Air t Purifier cabinet openings gradual transitions are recommended to reduce air turbulence and maximize efficiency No more than 20 degrees about 4 in per running ft of expansion should be used on each side of the transition fitting Turning Vanes If the Perfect Airt Purifier is installed adjacent to a 90 degree duct elbow turning ...

Page 3: ...of the Perfect Airt Purifier should be readily accessible Enough room should be provided for periodic replacement of the air purifier cartridges ELECTRICAL SHOCK AND UNIT DAMAGE HAZARD Failure to follow this warning could result in personal injury or death Only a trained experienced service person should install the Perfect Airt Purifier A thorough check of the unit installation should be complete...

Page 4: ...abinet between the furnace and return air duct see Fig 4 A transition duct may be required e Furnace adapters have been included for installer convenience They are designed for top or bottom mount installations see Fig 5 f Return air duct adapters have been included for installer convenience They should be used to connect the upstream side of the air purifier cabinet to the return air duct see Fig...

Page 5: ...ply connector see Fig 7 d Route the power cord through nearest cabinet hole and protect with enclosed cable connector Zip ties have been enclosed to secure the power cord to the side of the power supply e Attach the quick connect terminals to the furnace EAC 1 and EAC 2 spade connections Attach the ground ring to furnace chassis ground NOTE The Perfect Airt Purifier is to be powered by 115v 60 Hz ...

Page 6: ...s the safety switch is activated b Turn the HVAC system power on and adjust the thermostat or Evolutiont System Control to activate the system fan c Turn the Perfect Airt Purifier power switch to on position d The power indicator light above the Air Purifier power switch should illuminiate see Fig 8 e Check to ensure the light goes off when the Perfect Airt Purifier power switch is set to off when...

Page 7: ...e electrical components Disconnect power between checks and then proceed carefully WARNING The Perfect Airt Purifier is equipped with a power indicator light located on the door see Fig 8 This power indicator light will illuminate when the Perfect Airt Purifier door is installed the power switch is in the on position AND the furnace blower is running If the power indicator light is not illuminated...

Page 8: ... EAC terminals 115v 60 Hz from furnace EAC terminals Maximum Airflow CFM 1600 2000 Efficiency Equivalent to MERV 15 Equivalent to MERV 15 Replacement Cartridge GAPBBCAR1625 GAPBBCAR2025 Dimensions GAPAAXBB1625 GAPAAXBB2025 A 18 3 8 21 7 8 B 15 1 8 18 5 8 C 11 1 8 11 1 8 D 17 1 2 21 E 22 1 8 22 1 8 F 25 1 4 25 1 4 7 16 Typical Top Bottom 1 3 16 1 3 16 1 3 16 1 15 16 A C E F B D A06069 Fig 10 Dimens...

Page 9: ...to the distributor through a registered servicing dealer for credit 4 All work shall be performed during normal working hours LIMITATIONS OF WARRANTIES ALL IMPLIED WARRANTIES INCLUDING IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE HEREBY LIMITED IN DURATION TO THE PERIOD FOR WHICH THE LIMITED WARRANTY IS GIVEN AND APPLIES SOME STATES DO NOT ALLOW LIMITATIONS ON HOW...

Page 10: ...or change at any time specifications or designs without notice and without incurring obligations EBryant Heating Cooling Systems 7310 W Morris St Indianapolis IN 46231 Printed in China Edition Date 3 06 Replaces II GAPA 0 1 Catalog No II GAPA 0 2 GAPA ...

Reviews: