9
Table 1 – Physical Data -- Unit 677C----A
UNIT SIZE
24040
24060
30040
30060
36060
36090
42060
42090
NOMINAL CAPACITY ---ton
2
2
2--- 1/2
2--- 1/2
3
3
3--- 1/2
3--- 1/2
SHIPPING WEIGHT ---lb.
(kg)
368
167
368
167
378
171
378
171
450
204
450
204
491
223
491
223
COMPRESSORS
Scroll
Quantity
1
REFRIGERANT (R---410A)
Quantity ---lb
(kg)
9.5
4.3
9.5
4.3
10.5
4.8
10.5
4.8
9.0
4.1
9.0
4.1
14.0
6.4
14.0
6.4
REFRIGERANT METERING
DEVICE
Indoor--- TXV, Outdoor--- Accurater
OUTDOOR ORIFICE
in. (qty)
(mm)
0.032 (2)
.81
0.032 (2)
.81
0.038 (2)
.97
0.038 (2)
.97
0.040 (2)
1.02
0.040 (2)
1.02
0.038 (Left OD Coil)
0.040 (Right OD Coil)
.97/1.02
OUTDOOR COIL
Rows...Fins/in.
Face Area---sq ft
2...21
13.6
2...21
13.6
2...21
15.4
2...21
15.4
2...21
13.6
2...21
13.6
2...21
19.4
2...21
19.4
OUTDOOR FAN
Nominal Cfm
Diameter---in.
(mm)
Motor Hp (Rpm)
2500
22
559
1/8 (825)
2500
22
559
1/8 (825)
2600
22
559
1/8 (825)
2600
22
559
1/8 (825)
3000
22
559
1/4 (1100)
3000
22
559
1/4 (1100)
3500
22
559
1/8 (825)
3500
22
559
1/8 (825)
INDOOR COIL
Rows...Fins/in.
Face Area---sq ft
3...17
3.7
3...17
3.7
3...17
3.7
3...17
3.7
3...17
4.7
3...17
4.7
3...17
4.7
3...17
4.7
INDOOR BLOWER
Nominal Cooling Airflow---(CFM)
Size---in.
(mm)
Motor ---hp
800
10x10
254x254
1/2
800
10x10
254x254
1/2
1000
10x10
254x254
1/2
1000
10x10
254x254
1/2
1200
11x10
279x254
3/4
1200
11x10
279x254
3/4
1400
11x10
279x254
3/4
1400
11x10
279x254
3/4
FURNACE SECTION*
Burner Orifice
Natural Gas Qty...Drill Size
Propane GasQty...Drill Size
2...44
2...55
2...38
2...53
2...44
2...55
2...44
2...53
2...38
2...53
3...38
3...53
2...38
2...53
3...38
3...53
HIGH---PRESSURE SWITCH
(psig) Cut---out
Reset (Auto)
650 +/--- 15
420 +/--- 25
LOSS---OF---CHARGE /
LOW---PRESSURE SWITCH
(Liquid Line) (psig)
Cut---out
Reset (auto)
20 +/--- 5
45 +/--- 10
RETURN---AIR FILTERS †
}
Throwaway (in.)
(mm)
20x20x1
508x508x25
20x24x1
508x610x25
24x30x1
610x762x25
*Based on altitude of 0 to 2000 ft (0---610 m).
{
Required filter sizes shown are based on the larger of the ARI (Air Conditioning and Refrigeration Institute) rated cooling airflow or the heating airflow velocity of
300 ft/minute for high---capacity type. Air filter pressure drop for non---standard filters must not exceed 0.08 IN. W.C.
}
If using accessory filter rack refer to filter rack installation instructions for correct filter size and quantity.
Horizontal Duct Covers
A09076
Basepan
Downflow
(Vertical)
Supply
Knockout
Basepan
Downflow
(Vertical)
Return
Knockout
A09077
Fig. 8 -- Supply and Return Duct Opening
1
2
2
1
3
3
4
4
1. Score groove in corner 1 in both directions as far as you can reach.
2. Starting in corner 1, tap-out all sides with a small hammer. Be careful
not to damage any other part of unit.
3. If side from corner 3 to 4 is not accessible due to heat exchanger,
pivot panel up and down by hand until remaining side breaks off.
INSTRUCTIONS FOR REMOVING DOWNSHOT PANELS
A09054
Fig. 9 -- Vertical (Downflow) Discharge Duct Knockouts
677C
--
--
A
Summary of Contents for 677C--A
Page 3: ...3 A09146 Fig 2 677C A24 30 Unit Dimensions 677C A ...
Page 4: ...4 A09147 Fig 3 677C A36 60 Unit Dimensions 677C A ...
Page 24: ...24 A09068 Fig 15 208 230 1 60 Wiring Diagram Unit 677C A 677C A ...
Page 25: ...25 A09209 Fig 16 208 230 3 60 Wiring Diagram Unit 677C A 677C A ...
Page 26: ...26 50VT500173 REV 4 0 A09099 Fig 17 Cooling Charging Table Subcooling 677C A ...