background image

NOTE:

Read the entire instruction manual before starting the

installation.

This symbol

indicates a change since the last issue.

TABLE OF CONTENTS

SAFETY CONSIDERATIONS .....................................................1

Introduction ....................................................................................2

RECEIVING AND INSTALLATION ..........................................2

Check Equipment......................................................................2

IDENTIFY UNIT ................................................................2
INSPECT SHIPMENT ........................................................2

Provide Unit Support ................................................................3

ROOF CURB & SLAB MOUNT.......................................3

Provide Clearances....................................................................4
Select and Install Ductwork .....................................................5
Rig and Place Unit....................................................................6

INSTALLATION ................................................................8

Connect Condensate Drain .......................................................9
Install Duct Connections ..........................................................9

CONFIGURING UNITS FOR DOWNFLOW (VERTI-
CAL) DISCHARGE-STANDARD UNITS (024–042)....11
CONFIGURING UNITS FOR DOWNFLOW (VERTI-
CAL) DISCHARGE-ECM UNITS (048–060) .................13

Install Electrical Connection ..................................................14

HIGH-VOLTAGE & CONTROL-VOLTAGE CONNEC-
TIONS................................................................................14
SPECIAL PROCEDURES FOR 208-V OPERATION ...15

PRE-START-UP ..........................................................................15

START-UP ...................................................................................17

CHECK FOR REFRIGERANT LEAKS..........................17
START UP AND MAKE ADJUSTMENTS....................18
CHECKING COOLING CONTROL OPERATION .......18
CHECKING HEATING CONTROL OPERATION........18
CHECKING

AND

ADJUSTING

REFRIGERANT

CHARGE ...........................................................................18
INDOOR

AIRFLOW

AND

AIRFLOW

ADJUST-

MENTS ..............................................................................21
For 208/230v-PSC Blower Motor.....................................21
For 208/230v-ECM Blower Motor ...................................21
COOLING SEQUENCE OF OPERATION .....................22
HEATING SEQUENCE OF OPERATION .....................23

MAINTENANCE.........................................................................23

AIR FILTER......................................................................24
UNIT TOP REMOVAL ....................................................24
INDOOR BLOWER AND MOTOR ................................24
OUTDOOR COIL, INDOOR COIL, AND CONDENSATE
DRAIN PAN......................................................................27
OUTDOOR FAN...............................................................28
ELECTRICAL CONTROLS AND WIRING ..................28
REFRIGERANT CIRCUIT...............................................29
INDOOR AIRFLOW ........................................................29
METERING DEVICE — ACUTROL DEVICE .............29
LIQUID LINE STRAINER ..............................................29

Troubleshooting............................................................................31

Start-Up Checklist ........................................................................32

NOTE TO INSTALLER — Before the installation, READ THESE
INSTRUCTIONS CAREFULLY AND COMPLETELY. Also,
make sure the User’s Manual and Replacement Guide are left with
the unit after installation.

SAFETY CONSIDERATIONS

Installation and servicing of air-conditioning equipment can be
hazardous due to system pressure and electrical components. Only
trained and qualified personnel should install, repair, or service
air-conditioning equipment.

Untrained personnel can perform basic maintenance functions of
cleaning coils and filters. All other operations should be performed
by trained service personnel. When working on air-conditioning
equipment, observe precautions in the literature, tags, and labels
attached to the unit, and other safety precautions that may apply.

Follow all safety codes. Wear safety glasses and work gloves. Use
quenching cloth for unbrazing operations. Have fire extinguisher
available for all brazing operations. Consult a qualified installer or
service agency for information or assistance. The qualified in-
staller or agency must use only factory-authorized kits or acces-
sories when modifying this product.

WARNING:

Before performing service or maintenance

operations on system, turn off power to unit. Turn off
accessory heater power switch, if applicable. Electrical
shock can cause personal injury.

Recognize safety information. This is the safety-alert symbol

.

When you see this symbol in instructions or manuals, be alert to
the potential for personal injury.

Understand the signal words DANGER, WARNING, CAUTION,
and NOTE. These words are used with the safety-alert symbol.
DANGER identifies the most serious hazards which will result in

Fig. 1—Unit 657A with Optional Base Rails

C95002

Installation, Start-Up
and Operating Instructions

657A
SINGLE PACKAGED
HEAT PUMP UNITS

Cancels:

II 657A.24.4

II 657A.24.5

7–03

—1—

Summary of Contents for 657A

Page 1: ...Also make sure the User s Manual and Replacement Guide are left with the unit after installation SAFETY CONSIDERATIONS Installation and servicing of air conditioning equipment can be hazardous due to...

Page 2: ...s 2 5 for unit dimensions All units are shipped in a horizontal discharge configuration for installation on a ground level slab All units can be converted to down flow discharge configurations for roo...

Page 3: ...h the roof curb Improperly applied gasketing also can result in air leaks and poor unit performance Curb should be level to within 1 4 in See Fig 8 This is necessary for unit drain to function properl...

Page 4: ...maximum horizontal extension of a partial overhang must not exceed 48 in IMPORTANT Do not restrict outdoor airflow An air restriction at either the outdoor air inlet or the fan discharge may be detri...

Page 5: ...unit has duct flanges on the supply and return air openings on the side of the unit See Fig 2 5 for connection sizes and locations When designing and installing ductwork consider the following CAUTIO...

Page 6: ...2 Heater limit switches may trip at air quantities below those recommended NOTE A 90 degree elbow must be provided in the supply ductwork to comply with UL Underwriters Laboratories codes for use with...

Page 7: ...recommended to be used for rigging Install brackets as follows Fig 7 657A Rigging Instructions UNIT SIZE CHART A CHART B Max Weight A B Max Weight C D LB KG IN MM IN MM LB KG IN MM IN MM 024 296 134...

Page 8: ...tional information Lifting holes are provided in base rails as shown in Fig 7 See Detail A or B B Refer to rigging instructions on unit A INSTALLATION 1 Position the lifting bracket assembly around th...

Page 9: ...ast 1 in lower than the unit drain pan condensate connection to prevent the pan from overflowing Prime the trap with water Connect a drain tube using a minimum of 3 4 in PVC 3 4 in CPVC or 3 4 in copp...

Page 10: ...uct Cover C95015 Fig 14 Indoor Blower Access Panel C950016 INDOOR BLOWER ACCESS PANEL REMOVE SCREWS Fig 15 Converting Blower Assembly to Vertical Airflow C950010 PLUG ASSEMBLIES RACEWAY FILLER BRACKET...

Page 11: ...oles in duct flanges as templates drill the remaining holes with the no 26 147 in drill 5 Fully secure the duct flanges using the remaining screws provided NOTE The finished kit installation accommoda...

Page 12: ...perimeter of the vertical discharge opening cover See Fig 13 9 Using a straight edge and sharp knife cut the insulation around the perimeter of the cover Remove the screws TABLE 1 PHYSICAL DATA UNIT...

Page 13: ...nit base Secure using screw removed in Step 7 Reconnect indoor fan motor leads and insert wire tie back into unit control box 13 Cover the horizontal duct openings Duct covers can be ordered as an acc...

Page 14: ...ground to minimize the pos sibility of personal injury if an electrical fault should occur This ground may consist of an electrical wire connected to the unit ground lug in the control compart ment o...

Page 15: ...the red lead to the contactor terminal from which the orange lead was disconnected 5 Using the wire nut removed from the red lead insulate the loose terminal on the orange lead 6 Wrap the wire nut wit...

Page 16: ...60 70 70 80 100 100 22 5 26 0 33 7 39 1 45 1 50 1 67 9 78 1 25 30 35 40 50 60 70 80 22 8 30 30 036 208 230 1 187 253 16 0 88 0 1 2 2 6 3 75 5 00 5 60 7 50 7 50 10 0 11 30 15 0 18 1 20 8 27 1 31 3 36 1...

Page 17: ...no additional leaks are not found 5 Charge unit with R 22 refrigerant using a volumetric charging cylinder or accurate scale Refer to unit rating plate for required charge Be sure to add extra refrige...

Page 18: ...room tem perature Observe that compressor outdoor fan and indoor blower motors start Observe that compressor and outdoor fan shut down when control setting is satisfied and that indoor blower shuts do...

Page 19: ...Fig 26 Wiring Diagram 024 to 042 208 230 60 1 C95037 19...

Page 20: ...Fig 27 Wiring Diagram 048 to 060 208 230 60 1 with ECM Indoor C95038 20...

Page 21: ...from obstructions and adjusted properly WARNING Disconnect electrical power to the unit and install lockout tag before changing blower speed Elec trical shock can cause serious injury or death Airflo...

Page 22: ...simultaneously through the Y and G terminals of the thermostat respectively On units with a compressor time delay relay there is a built in 5 minute 45 seconds delay between compressor starts Energiz...

Page 23: ...AT RANGE VIO setting or the AC HP SIZE BLU setting whichever is greater This may be a noticeable change in airflow When thermostat is satisfied contacts open deenergizing contactor and relay motors an...

Page 24: ...C INDOOR BLOWER AND MOTOR NOTE Motors without oilers are prelubricated Do not attempt to lubricate these motors For longer life operating economy and continuing efficiency clean accumulated dirt and g...

Page 25: ...1200 1400 1600 1800 2000 2200 5 20 0 030 0 033 0 037 0 042 0 047 0 052 0 060 0 067 0 075 TABLE 12 FILTER PRESSURE DROP IN WG UNIT SIZE FILTER SIZE IN 500 600 700 800 900 1000 1100 1200 1300 1400 1500...

Page 26: ...5 6 24 1 25 0 33 3 34 8 33 8 32 6 31 8 31 0 30 2 80 16 4 17 6 21 4 16 8 23 2 31 8 32 2 31 3 30 4 29 5 28 6 85 9 4 8 6 14 7 21 6 29 4 29 8 28 9 27 8 27 0 90 11 6 18 9 26 4 27 3 26 4 25 5 95 3 7 10 8 18...

Page 27: ...21 6 23 0 24 4 24 5 24 6 80 8 9 8 9 8 9 12 4 16 0 19 4 21 0 22 4 23 8 24 0 24 0 85 8 2 8 2 8 2 11 8 15 3 18 7 20 2 21 8 23 3 23 4 23 4 90 7 7 7 7 7 7 10 8 13 7 16 7 18 7 20 7 22 7 22 7 22 9 95 7 2 7...

Page 28: ...NOTE Refer to the heating and or cooling sequence of operation in this publication as an aid in determining proper control operation TABLE 13H SUPERHEAT CHARGING TABLE UNIT 060 TEMP F AIR ENT COND EV...

Page 29: ...evices that are of the fixed orifice type located in the header to the indoor and outdoor coils J LIQUID LINE STRAINER The liquid line strainer to protect metering device is made of wire mesh and loca...

Page 30: ...ay valve and is directed to the cooling liquid line check valve It is then condensed and directed through subcooling circuits and out to the strainer and the check valve in the heating liquid line 2 T...

Page 31: ...Dirty air filter Replace filter Dirty indoor or outdoor coil Clean coil Refrigerant overcharged Recover excess refrigerant Air in system Recover refrigerant evacuate system and recharge Heat Indoor a...

Page 32: ...ghtness III START UP Supply Voltage C S __________ S R __________ R C __________ Compressor Amps C __________ S __________ R __________ Indoor Evaporator Fan Amps __________ TEMPERATURE Outdoor Conden...

Reviews: